Table 108: Setting: Resistance Measurement (Potentiometer) - WAGO 750-489 Manual

4ai rtd/tc/strain gauge ex i, 4-channel analog input, rtd/tc/strain gauge, intrinsically safe for wago-i/o-system 750 series
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-489 4AI RTD/TC/Strain Gauge Ex i
4.7.7.2
S5-FB250 Format
With the "Potentiometer" setting and S5-FB250 format enabled, the I/O module
outputs the resistance normalized to 2000. The defined measuring range of
0 % ... 100 % corresponds to a possible process value of 0 ...+2000.
Note:
Be aware that the status information is represented in bit 0 ... bit 2 and the
digitized measured value in bit 3 ... bit 15. Therefore, the normalized measured
value is shifted by three bits in the process image!
Thus a normalized measured value of +2000 corresponds to a process value of
+16000
Table 108: Setting: Resistance Measurement (Potentiometer) – S5-FB250 Format
Percent [%]
≤ 0.0
0.0
25.0
50.0
75.0
100.0
100.05
105.0
≥ 155.05
1)
Status bits: X= not used, F= error, Ü= overflow
Numeric Value
Binary
XFÜ
1)
'1000.0000.0000.0
010'
'0000.0000.0000.0
000'
'0000.1111.1010.0
000'
'0001.1111.0100.0
000'
'0010.1110.1110.0
000'
'0011.1110.1000.0
000'
'0011.1110.1000.1
001'
'0100.0001.1010.0
001'
'0111.1111.1111.1
010'
Status
Byte,
Hex.
Dec.
Hex.
0x8002
-32766
0x50
0x0000
0
0x0FA0
4000
0x1F40
8000
0x00
0x2EE0
12000
0x3E80
16000
0x3E89
16009
0x42
0x41A1
16800
0x7FFA
32762
0x60
Version 1.1.0, valid from FW Version 02
Process Image
93
Error
Range
LED
On
Underflow
Nominal
Off
range
On
Overrange
On
Overflow