WAGO-I/O-SYSTEM 750
750-489 4AI RTD/TC/Strain Gauge Ex i
4.6.3.9
TC Type K – Standard Format/Kelvin
Table 83: TC Type K Setting – Standard Format/Kelvin
Temperature
[K]
≤ 48.1
48.2
73.1
73.2
1645.2
1645.3
1670.2
≥ 1670.3
4.6.3.10
TC Type K – S5-FB250 Format/Kelvin
Table 84: TC Type K Setting – S5-FB250 Format/Kelvin
Temperature
[K]
≤ 47.0
48.0
72.0
73.0
1645.0
1646.0
1670.0
≥ 1671.0
1)
Status bits: X= not used, F= error, Ü= overflow
Numeric Value
Binary
'1000.0000.0000.0000'
'0000.0001.1110.0010'
'0000.0010.1101.1011'
'0000.0010.1101.1100'
'0100.0000.0100.0100'
'0100.0000.0100.0101'
'0100.0001.0011.1110'
'0111.1111.1111.1111'
Numeric Value
Binary
XFÜ
1)
'1000.0000.0000.0
010'
'0000.0001.1000.0
001'
'0000.0010.0100.0
001'
'0000.0010.0100.1
000'
'0011.0011.0110.1
000'
'0011.0011.1100.0
001'
'0011.0100.0011.0
001'
'0111.1111.1111.1
010'
Status
Byte,
Hex.
Dec.
Hex.
0x8000
-32768
0x50
0x01E2
482
0x41
0x02DB
731
0x02DC
732
0x00
0x4044
16452
0x4045
16453
0x42
0x413E
16702
0x7FFF
32767
0x60
Status
Byte,
Hex.
Dec.
Hex.
0x8002
-32766
0x50
0x0181
385
0x41
0x0241
577
0x0248
584
0x00
0x3368
13160
0x33C1
13249
0x42
0x3431
13361
0x7FFA
32762
0x60
Version 1.1.0, valid from FW Version 02
Process Image
79
Error
Range
LED
On
Underflow
On
Underrange
Nominal
Off
range
On
Overrange
On
Overflow
Error
Range
LED
On
Underflow
On
Underrange
Nominal
Off
range
On
Overrange
On
Overflow
Manual