WAGO-I/O-SYSTEM 750
750-489 4AI RTD/TC/Strain Gauge Ex i
4.5.3.3
TC Type C – Standard Format/Fahrenheit
Table 53: TC Type C Setting – Standard Format/Fahrenheit
Temperature
[°F]
≤ -13.1
-13.0
31.9
32.0
3270.0
3270.1
3275.0
≥ 3275.1
1)
Process values below 0 are represented in binary form as the two's complement.
4.5.3.4
TC Type C – S5-FB250 Format/Fahrenheit
Table 54: TC Type C Setting – S5-FB250 Format/Fahrenheit
Temperature
[°F]
≤ -14.0
-13.0
31.0
32.0
3270.0
3271.0
3275.0
≥ 3276.0
1)
Status bits: X= not used, F= error, Ü= overflow
Numeric Value
Binary
'1000.0000.0000.0000'
'1111.1111.0111.1110'
'0000.0001.0011.1111'
'0000.0001.0100.0000'
'0111.1111.1011.1100'
'0111.1111.1011.1101'
'0111.1111.1110.1110'
'0111.1111.1111.1111'
Numeric Value
Binary
XFÜ
1)
'1000.0000.0000.0
010'
'1111.1111.0011.1
001'
'0000.0000.1111.1
001'
'0000.0001.0000.0
000'
'0110.0110.0011.0
000'
'0110.0110.0011.1
001'
'0110.0110.0101.1
001'
'0111.1111.1111.1
010'
1)
Status
Byte,
Hex.
Dec.
Hex.
0x8000
-32768
0x50
0xFF7E
-130
0x41
0x013F
319
0x0140
320
0x00
0x7FBC
32700
0x7FBD
32701
0x42
0x7FEE
32750
0x7FFF
32767
0x60
Status
Byte,
Hex.
Dec.
Hex.
0x8002
-32766
0x50
0xFF99
-103
0x41
0x00F9
249
0x0100
256
0x00
0x6630
26160
0x6639
26169
0x42
0x6659
26201
0x7FFA
32762
0x60
Version 1.1.0, valid from FW Version 02
Process Image
63
Error
Range
LED
On
Underflow
On
Underrange
Nominal
Off
range
On
Overrange
On
Overflow
Error
Range
LED
On
Underflow
On
Underrange
Nominal
Off
range
On
Overrange
On
Overflow
Manual