Tc Type T - Standard Format/Kelvin; Tc Type T - S5-Fb250 Format/Kelvin; Table 89: Tc Type T - Standard Format/Kelvin; Table 90: Tc Type T Setting - S5-Fb250 Format/Kelvin - WAGO 750-489 Manual

4ai rtd/tc/strain gauge ex i, 4-channel analog input, rtd/tc/strain gauge, intrinsically safe for wago-i/o-system 750 series
Table of Contents

Advertisement

82
Process Image
4.6.3.15
TC Type T – Standard Format/Kelvin
Table 89: TC Type T – Standard Format/Kelvin
Temperature
[K]
≤ 48.1
48.2
73.1
73.2
673.2
673.3
698.2
≥ 698.3
4.6.3.16
TC Type T – S5-FB250 Format/Kelvin
Table 90: TC Type T Setting – S5-FB250 Format/Kelvin
Temperature
[K]
≤ 47.0
48.0
72.0
73.0
673.0
674.0
698.0
≥ 699.0
1)
Status bits: X= not used, F= error, Ü= overflow
Manual
Version 1.1.0, valid from FW Version 02
Numeric Value
Binary
'1000.0000.0000.0000'
'0000.0001.1110.0010'
'0000.0010.1101.1011'
'0000.0010.1101.1100'
'0001.1010.0100.1100'
'0001.1010.0100.1101'
'0001.1011.0100.0110'
'0111.1111.1111.1111'
Numeric Value
Binary
XFÜ
1)
'1000.0000.0000.0
010'
'0000.0001.1000.0
001'
'0000.0010.0100.0
001'
'0000.0010.0100.1
000'
'0001.0101.0000.1
000'
'0001.0101.0001.0
001'
'0001.0101.1101.0
001'
'0111.1111.1111.1
010'
WAGO-I/O-SYSTEM 750
750-489 4AI RTD/TC/Strain Gauge Ex i
Status
Byte,
Hex.
Dec.
Hex.
0x8000
-32768
0x50
0x01E2
482
0x41
0x02DB
731
0x02DC
732
0x00
0x1A4C
6732
0x1A4D
6733
0x42
0x1B46
6982
0x7FFF
32767
0x60
Status
Byte,
Hex.
Dec.
Hex.
0x8002
-32766
0x50
0x0181
385
0x41
0x0241
577
0x0248
584
0x00
0x1508
5384
0x1511
5393
0x42
0x15D1
5585
0x7FFA
32762
0x60
Error
Range
LED
On
Underflow
On
Underrange
Nominal
Off
range
On
Overrange
On
Overflow
Error
Range
LED
On
Underflow
On
Underrange
Nominal
Off
range
On
Overrange
On
Overflow