Voltage Measurement 1 (±30 Mv); Table 109: Setting Voltage Measurement 1 (±30 Mv) - Standard Format; Table 110: Setting Voltage Measurement 1 (±30 Mv) - S5-Fb250 Format - WAGO 750-489 Manual

4ai rtd/tc/strain gauge ex i, 4-channel analog input, rtd/tc/strain gauge, intrinsically safe for wago-i/o-system 750 series
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-489 4AI RTD/TC/Strain Gauge Ex i
Representation in the tables: Corresponding monitoring must be switched
on!
The "Underflow", "Overflow", "Underrange" and "Overrange" areas require that
the corresponding monitoring is switched on (see Section "Diagnostics" >
"Behavior of the I/O Module in the Event of Error").
4.8.1
Voltage Measurement 1 (±30 mV)
4.8.1.1
Standard Format
Table 109: Setting Voltage Measurement 1 (±30 mV) – Standard Format
Voltage [mV]
≤ -35.0012
-35.0
-30.0012
-30.0
-15.0
15.0
30.0
30.0012
35.0
≥ 35.0012
1)
Process values below 0 are represented in binary form as the two's complement.
4.8.1.2
S5-FB250 Format
Table 110: Setting Voltage Measurement 1 (±30 mV) – S5-FB250 Format
Voltage [mV]
≤ -35.012
-35.0
-30.012
-30.0
-15.0
15.0
30.0
30.012
35.0
≥ 35.012
1)
Status bits: X= not used, F= error, Ü= overflow
Numeric Value
Binary
'1000.0000.0000.0000' 0x8000
'1000.1110.0001.0001' 0x8E11
'1001.1110.0101.0111' 0x9E57
'1001.1110.0101.1000' 0x9E58
'1100.1111.0010.1100' 0xCF2C
'0011.0000.1101.0100' 0x30D4
'0110.0001.1010.1000' 0x61A8
'0110.0001.1010.1001' 0x61A9
'0111.0001.1110.1110' 0x71EE
'0111.1111.1111.1111' 0x7FFF
Numeric Value
Binary
XFÜ
1)
'1000.0000.0000.0
010'
'1010.0100.1111.0
001'
'1011.0001.1101.1
001'
'1011.0001.1110.0
000'
'1101.1000.1111.0
000'
'0010.0111.0001.0
000'
'0100.1110.0010.0
000'
'0100.1110.0010.1
001'
'0101.1100.0010.0
001'
'0111.1111.1111.1
010'
Status
1)
Byte,
Hex.
Dec.
Hex.
-32768
0x50
-29167
0x41
-25001
-25000
-12500
0x00
12500
25000
25001
0x42
29167
32767
0x60
Status
Byte,
Hex.
Dec.
Hex.
0x8002
-32766
0x50
0xA4E1
-23327
0x41
0xB1D9
-20007
0xB1E0
-20000
0xD8F0
-10000
0x00
0x2710
10000
0x4E20
20000
0x4E29
20009
0x42
0x5B21
23329
0x7FFA
32762
0x60
Version 1.1.0, valid from FW Version 02
Process Image
95
Error
Range
LED
Hex.
Binary
On
Underflow
On
Underrange
Nominal
Off
range
On
Overrange
On
Overflow
Error
Range
LED
Hex.
Binary
On
Underflow
On
Underrange
Nominal
Off
range
On
Overrange
On
Overflow
Manual

Advertisement

Table of Contents
loading

Table of Contents