136 Commissioning
Table 144: "Calibration" Menu Item, Channel 1 ... Channel 4
Parameter / Button
[Start Calibration]
Process value
Show values in
hexadecimal
[Area for displaying
errors]
The dialog of the started calibration process corresponds to the signal type
setting!
User calibration follows the same principle for temperature, voltage and
resistance measurement.
The content of the dialog windows differs according to the respective signal type
set previously!
Manual
Version 1.1.0, valid from FW Version 02
750-489 4AI RTD/TC/Strain Gauge Ex i
Setting Option / Description
Automatic calibration is started by clicking the [Start
Calibration] button.
A dialog prompts you to enter a reference
temperature, reference voltage or reference
resistance. Based on this voltage, correction values
are calculated as needed.
These correction values are permanently written to
the I/O module after the calibration.
This process can be repeated any number of times.
The process value can be constant or
[Output field]
deliberately kept changeable; it can
be represented as a fixed decimal
value with unit or as a hexadecimal,
according to the measurement range.
Hexadecimal representation can be switched on or
off.
Hexadecimal representation is
enabled.
Hexadecimal representation is
disabled.
Underflow
Underflow in the sensor lines
Overflow
Overflow in the sensor lines
Measuring
The field-side input voltage or field-
range
side input resistance is below the
underflow
measurement range lower limit.
Measuring
The field-side input voltage or field-
range overflow
side input resistance is above the
measurement range upper limit.
Internal Error
Internal error present (fieldbus power
supply undervoltage or ADC error)