Parameters/address space

4.1

Output ranges

The analog output module AQ 4×U/I ST has the following measuring ranges:
Table 4- 1
Output type
Current
Voltage
The tables of the output ranges, overflow, overrange, etc. can be found in section
Representation of analog values (Page 34).
16
Output ranges
Output ranges
± 20 mA
0 to 20 mA
4 to 20 mA
±10 V
±5 V
0 to 10 V
1 to 5 V
Resolution
16 bits including sign
15 bits
14 bits
16 bits including sign
15 bits including sign
15 bits
13 bits
Analog Output Module AQ 4xU/I ST (6ES7135-6HD00-0BA1)