Festo CPX-P-8DE-N Series Description page 87

Cpx terminal (-p) modules and connection blocks
Table of Contents

Advertisement

3. Input module CPX-P-8DE-N-...
Module parameter: Replacement value channel 0 ... 3
4828 + m * 64 + 14
Function no.
Description
Specifies the replacement value for the status bit of the respective channel which
is to be entered into the PII in the event of an error (short circuit or wire break)
(
of the respective channel.
Bit
Replacement value channel 0 ... 3
Bit: 1,
Values
Comment
Replacement value channel 4 ... 7
Tab. 3/28: Replacement value channel 0 ... 3 (channel-specific)
Module parameter: Replacement value channel 4 ... 7
Function no.
4828 + m * 64 + 15
Description
Bit
Replacement value channel 4 ... 7
Bit: 1,
Values
Comment
Replacement value channel 0 ... 3
Tab. 3/29: Replacement value channel 4 ... 7 (channel-specific)
Festo P.BE-CPX-P-EA-EN en 1209NH English
Tab. 3/9, bit in byte 0). An alteration of the parameter causes an initialisation
0
Duct 0
3,
2
Duct 1
5,
4
Duct 2
7,
6
Duct 3
0
0
Replacement value = 0 (presetting)
0
1
Replacement value = 1
1
0
last value of the status bit valid
1
1
Reserved
Tab. 3/28
0
Duct 4
3,
2
Duct 5
5,
4
Duct 6
7,
6
Duct 7
0
0
Replacement value = 0 (presetting)
0
1
Replacement value = 1
1
0
last value of the status bit valid
1
1
Reserved
Handheld
m = Module number (0 ... 47)
[Fault mode value]
[Ch 0]
[Ch 1]
[Ch 2]
[Ch 3]
[0]
[1]
[last value]
Tab. 3/29
Handheld
m = Module number (0 ... 47)
[Fault mode value]
[Ch 4]
[Ch 5]
[Ch 6]
[Ch 7]
[0]
[1]
[last value]
Tab. 3/28
3-37

Advertisement

Table of Contents
loading

Table of Contents