Page 2
Text designations: Activities that may be carried out in any order 1. Activities that should be carried out in the order stated – General lists è Result of an action/References to more detailed information Festo – CPX-4AE-4AA-H – 2017-12...
This document describes the mode of operation, mounting, installation and commissioning of the product. Certain aspects of use are described in other documents and must be observed è 1.1 Further applicable documents. Further applicable documents For all available product documentation è www.festo.com/pk Document Table of contents Brief description...
The product label is located on the top of the fibre-optic cable è Fig. 3. Scanning the printed Data Matrix Code with an appropriate device calls the Festo Support Portal, with information appropriate for the product. Alternatively, the Product Key (11-digit alphanumeric code on the product label) can be entered in the search field of the Support Portal.
Ensure that storage times are kept to a minimum. Intended use The analogue module is determined only for use in terminal CPX and terminal CPX-P of Festo. Operate the product only at suitable bus nodes CPX è Tab. 3.
– Spare parts è www.festo.com/spareparts – Documents and literature è www.festo.com/sp Service Contact your regional Festo contact person if you have technical questions è www.festo.com Product overview Function The analogue module with HART functionality provides analogue current inputs and current outputs and enables the recording and further processing of analogue current signals.
– Housing bottom part for electrical and mechanical linking of the CPX modules – Variant with connection possible for operating and load voltage – Mounting option for entire terminal CPX Tab. 5 Module components of analogue module Festo – CPX-4AE-4AA-H – 2017-12 English...
(PII). At the end of the cyclical program, the process image for the outputs (PIO) is transferred to the output modules as a signal status. Primary Value Quaternary Value Secondary Value Tertiary Value Tab. 7 Product-specific terms and abbreviations Festo – CPX-4AE-4AA-H – 2017-12 English...
– The connection block has a recess for a coding piece at the bottom. – Connection block in pre-assembled CPX terminals are mechanically coded at the factory. Fig. 4 Coding pin on the electronics module Festo – CPX-4AE-4AA-H – 2017-12 English...
Page 14
3. Align the plug connector of the connection block with the plug connector of the electronics module. 4. Push the connection block onto the electronics module without tilting until the coding piece in the connection block engages. Festo – CPX-4AE-4AA-H – 2017-12 English...
Page 15
1. Lay the connection block 4 on a flat surface, top side first. 2. Unlock and remove the cover 1. 3. Press out the coding piece 3 using a suitable tool 2. 4. Push the cover onto the plug connector of the connection block 5. Festo – CPX-4AE-4AA-H – 2017-12 English...
2. Loosen the screws of the connection block. 3. Pull the connection block out of the plug connector of the electronics module without tilting. 4. Pull the electronics module out of the contact rails of the interlinking block without tilting. Festo – CPX-4AE-4AA-H – 2017-12 English...
Page 20
3. Pull the connection block out of the plug connector of the electronics module without tilting. 4. Set the DIL switches on the electronics module. 5. Mount the connection block è Chap. 6.3. è The process image becomes effective after switching on the power supply. Festo – CPX-4AE-4AA-H – 2017-12 English...
The metal thread of socket contact M12 is internally connected to the earth terminal of terminal CPX and can be used as a screen connection. Only use suitable plug connectors è www.festo.com/catalogue Seal unused connections with protective caps ISK-M12 è Accessories.
1) Connection and display components è Fig. 3. Tab. 10 Pin allocation on terminal connection block CPX-P-AB-2XKL-8POL Connection blocks CPX-P-AB-2XKL-8POL do not feature a connection for the cable screening. Set up the screening or equipotential bonding separately. Festo – CPX-4AE-4AA-H – 2017-12 English...
Page 23
Tab. 11 Specifications for spring-loaded terminal Only use suitable terminal strips è www.festo.com/catalogue Connect only one conductor per spring-loaded terminal. With a screwdriver, press the unlocking pin and insert the conductor end with the wire end sleeve into the terminal opening to the limit stop.
Page 24
[mm] Tab. 12 Specifications for screw terminal Only use suitable terminal strips è www.festo.com/catalogue Connect only one conductor per screw terminal. Loosen the screw terminal, insert the conductor end with wire end sleeve and tighten the screw terminal (tightening torque: 0.5 … 0.6 Nm).
7.4.4 Mechanically coding the terminal connection The terminal connection can be mechanically coded with a coding system. The coding system is optionally available è www.festo.com/catalogue. Recommendation: provide each contact with a coding element. Terminal strip Coding tab for the recess on the box header...
+ 4 … 20 mA HART 24 V – L– HART input module: active HART transmitter: passive Fig. 13 3-wire connection of a passive HART transmitter Power supply for the HART transmitter via the HART input module Festo – CPX-4AE-4AA-H – 2017-12 English...
+ 4 … 20 mA HART AOUTx – L– HART output module: active HART actuator: passive Fig. 15 2-wire connection of a passive HART actuator Power supply for the HART actuator, HART communication and setpoint in the same circuit Festo – CPX-4AE-4AA-H – 2017-12 English...
+ 4 … 20 mA HART AOUTx – L– HART output module: passive Auxiliary energy HART actuator: active Fig. 16 4-wire connection of an active HART actuator Power supply for the HART actuator via the auxiliary energy Festo – CPX-4AE-4AA-H – 2017-12 English...
SW CH1 SW CH0 8 bytes 1) IW CH0 = actual value of channel 0 (input), SW CH1 = setpoint value of channel 1 (output), etc. Tab. 13 Process image for variants without HART variables Festo – CPX-4AE-4AA-H – 2017-12 English...
Depending on the higher-order control system, low byte and high byte may be organised differently. – If an invalid value has been determined, 0xFFFF is transmitted. – Determination of the HART variables to be transferred during parameterisation è Chap. 8.4. Festo – CPX-4AE-4AA-H – 2017-12 English...
CPX-4AE-4AA-H Parameterisation The CPX terminal and the module described here can be parameterised with the operator unit (CPX-MMI), the Festo Maintenance Tool (CPX-FMT) software or the higher-level system. 8.4.1 Recommended parameterisation sequence Changed parameters are not valid until a complete check and saving procedure have been performed (max.
SCS monitoring (sensor supply short-circuit/overload) Bit 1 … 6: Reserved Bit 7: Monitoring of parameterisation errors Values Bit 0, 7: Inactive Active (default) Tab. 16 Description of the “Module CPX monitoring, parameterisation of error control” module parameter Festo – CPX-4AE-4AA-H – 2017-12 English...
Page 34
Monitoring according to NAMUR NE43 Bit 7: Reserved Values Bit 0: Sign + 15 bits (presetting) Linear scaling Bit 4: Inactive (presetting) Active Tab. 18 Description of the “Data format, monitoring according to NAMUR NE43” module parameter Festo – CPX-4AE-4AA-H – 2017-12 English...
Page 35
Bit 4 … 6: Reserved Bit 7: Monitoring of parameterisation errors Values Bit 0 … 3: 0 = Inactive (presetting) Active Bit 7: Inactive Active (default) Tab. 19 Description of “Monitoring of channel 0 … 3” channel parameter Festo – CPX-4AE-4AA-H – 2017-12 English...
Page 36
Bit 0 … 7: Low byte or high byte as limit value Values Presetting: -27648 (low byte = 0, high byte = 148) Tab. 20 Description of “Lower limit value of channel 0 … 3” channel parameter Festo – CPX-4AE-4AA-H – 2017-12 English...
Page 37
Bit 0 … 7: Low byte or high byte as limit value Values Presetting: 27648 (low byte = 0, high byte = 108) Tab. 21 Description of “Upper limit value of channel 0 … 3” channel parameter Festo – CPX-4AE-4AA-H – 2017-12 English...
Page 38
– Error message (limit values and hysteresis è Fig. 17) Allocation Bit 0 … 7: Low byte or high byte of hysteresis Values Presetting: 0 (low byte = 0, high byte = 0) Tab. 23 Description of the “Limit monitoring hysteresis” module parameter Festo – CPX-4AE-4AA-H – 2017-12 English...
Page 39
– If the upper limit value is exceeded by the half hysteresis value, an error message is output. – If the upper limit value is undershot by the half hysteresis value, an error message extinguishes. Festo – CPX-4AE-4AA-H – 2017-12 English...
Page 40
0 … 20 mA Channel 3 Inactive 4 … 20 mA without HART 4 … 20 mA with HART 0 … 20 mA Tab. 25 Allocation and values of the “Signal range” channel parameter Festo – CPX-4AE-4AA-H – 2017-12 English...
Page 41
Smoothed over 4 values Smoothing over 8 values Channel 3 Inactive Smoothing over 2 values Smoothing over 4 values Smoothing over 8 values Tab. 27 Allocation and values of the “Smoothing factor” channel parameter Festo – CPX-4AE-4AA-H – 2017-12 English...
Page 42
Channel of HART variable 2 = channel 1 Channel of HART variable 2 = channel 2 Channel of HART variable 2 = channel 3 Tab. 29 Allocation and values of “IEEE variable of HART variable 1, HART variable 2” channel parameter Festo – CPX-4AE-4AA-H – 2017-12 English...
Page 43
Channel of HART variable 4 = channel 1 Channel of HART variable 4 = channel 2 Channel of HART variable 4 = channel 3 Tab. 30 Allocation and values of “IEEE variable of HART variable 3, HART variable 4” channel parameter Festo – CPX-4AE-4AA-H – 2017-12 English...
Page 44
Idle-Mode of channel 0 … 3: Hold Last State Fault State (presetting) Idle State of channel 0 … 3: Reset value (presetting) Set value Tab. 32 Description of “Idle-Mode of channel 0 … 3” module parameter Festo – CPX-4AE-4AA-H – 2017-12 English...
Page 45
Force-Mode of channel 0 … 3: Disabled (presetting) Force State Force State of channel 0 … 3: Reset value (presetting) Set value Tab. 33 Description of the “Forcing of channel 0 … 3” module parameter Festo – CPX-4AE-4AA-H – 2017-12 English...
D13 D12 D11 D10 D9 field Value Digital input value 1) VZ = sign (0 = positive, 1 = negative) Tab. 34 Data format of the module CPX-4AE-4AA-H – Range of values -32768 … 0 … 32767 Festo – CPX-4AE-4AA-H – 2017-12 English...
Digital input value Significance 4 … 20 mA -32768 … 32767 Nominal range, freely scalable < 1.19 mA -32768 Underflow Tab. 36 Range of values for scalable data format (input 4 … 20 mA) Festo – CPX-4AE-4AA-H – 2017-12 English...
22 mA Overflow -32768 … 0 … 32767 4 … 20 mA Nominal range, freely scalable < -32768 0 mA Underflow Tab. 40 Range of value for scalable data format (output 4 … 20 mA) Festo – CPX-4AE-4AA-H – 2017-12 English...
Lower limit value 10 mA 3000 Value in nominal range 20 mA 6000 Upper limit value 22 mA 6600 Limit value exceeded Tab. 43 Example of scaling and limit monitoring for a pressure sensor Festo – CPX-4AE-4AA-H – 2017-12 English...
The representation of errors in the bus nodes depends on the bus protocol è Description of bus nodes. A further possibility for diagnostics is the operator unit CPX-MMI. The operator unit displays the error messages in clear text è Description of operator unit CPX-MMI. Festo – CPX-4AE-4AA-H – 2017-12 English...
1) The module displays the error depending on the parameterisation. The digital input values are processed again. 2) The diagnostics are output with the first recorded input value and kept until valid input values have been recorded for at least 200 ms. Festo – CPX-4AE-4AA-H – 2017-12 English...
Page 54
1) The module displays the error depending on the parameterisation. The digital input values are processed again. 2) The diagnostics are output with the first recorded input value and kept until valid input values have been recorded for at least 200 ms. Tab. 44 Error messages of the analogue module Festo – CPX-4AE-4AA-H – 2017-12 English...
– The DIL switch is incorrectly set. Tab. 45 Indicator: module error LED Channel error indicator Each channel is assigned an LED. LED (red) Description Error-free operation Channel-specific errors è Tab. 44. Lights up Tab. 46 Indicator: channel error LED Festo – CPX-4AE-4AA-H – 2017-12 English...
Page 56
Channel active as output: – Signal range 4 … 20 mA with HART Flashes – HART communication error-free Channel active as output Lights up Tab. 48 Indicator: status LED for channel status of output Festo – CPX-4AE-4AA-H – 2017-12 English...
In accordance with EU explosion (Declaration of conformity è www.festo.com/sp) protection guideline (ATEX) In accordance with EU EMC Directive Note on materials RoHS compliant Information on materials – Housing PA reinforced Tab. 49 General technical data Festo – CPX-4AE-4AA-H – 2017-12 English...
Page 58
Sensor cable length Max. 500 (screened) Electrical isolation between channels None Electrical isolation between channel and internal bus Fuse protection (short circuit) Per channel Analogue outputs Load resistance [Ω] Max. 750 Tab. 50 Electrical data Festo – CPX-4AE-4AA-H – 2017-12 English...
Page 60
Copyright: Festo AG & Co. KG Ruiter Straße 82 73734 Esslingen Germany Phone: +49 711 347-0 Fax: +49 711 347-2144 Reproduction, distribution or sale of this document or communica E-mail: tion of its contents to others without express authorization is service_international@festo.com...