3. Input module CPX-P-8DE-N-...
Module parameter: Input debounce time channel 4 ... 7
Function no.
4828 + m * 64 + 13
Description
Bit
Input debounce time channel 4 ... 7
Bit: 1,
Values
Comment
Tab. 3/27: Input debounce time channel 4 ... 7 (channel-specific)
3-36
Detailed information regarding the input debounce time can
be found in the CPX system description. The parameter,
however, is module-specific for many other input modules
and influences the behaviour of the entire module. In the
CPX-P-8DE-N-... it is a channel-specific parameter that spe-
cifies the behaviour of an individual channel.
Tab. 3/26
0
Duct 4
3,
2
Duct 5
5,
4
Duct 6
7,
6
Duct 7
0
0
Disabled
0
1
3 ms (presetting)
1
0
10 ms
1
1
20 ms
Tab. 3/26
Handheld
m = Module number (0 ... 47)
[Input debounce time]
[Ch 4]
[Ch 5]
[Ch 6]
[Ch 7]
[Inactive]
[3 ms]
[10 ms]
[20 ms]