Circuitry Examples Cpx-P-8De-N - Festo CPX-P-8DE-N Series Description

Cpx terminal (-p) modules and connection blocks
Table of Contents

Advertisement

3. Input module CPX-P-8DE-N-...

3.2.3 Circuitry examples CPX-P-8DE-N..

1
Namur sensor
Fig. 3/2: Connection of Namur sensors
1
Actuated
mechanical
contact
Fig. 3/3: Connection of actuated mechanical contacts
Festo P.BE-CPX-P-EA-EN en 1209NH English
Connection of Namur sensors
Namur sensors are supplied via the module and deliver a
high or low logic signal depending on the switching status of
the sensor. A possible wire break or short circuit is detected
via an internal current measurement. A corresponding error
message is generated depending on parameterisation.
Connection of actuated mechanical contacts
Actuated mechanical contacts also enable a wire break and
short-circuit monitoring function. The two resistors ensure
the current lies within the valid operating range in both
switching states.
10 ... 22 kΩ
1 ... 2 kΩ
1
1
3-9