Festo CPX-P-8DE-N Series Description page 81

Cpx terminal (-p) modules and connection blocks
Table of Contents

Advertisement

3. Input module CPX-P-8DE-N-...
Module parameter: Monitoring limit values
This parameter is only available in the extended process image (miniature switch = ON).
4828 + m * 64 + 7
Function no.
Description
Specifies the diagnostic response upon reaching limit values (operating mode B)
or falling below/exceeding limit values (operating mode C, D).
If monitoring is active, a diagnostic message is sent to the bus node in the corres-
ponding case and the channel error LED illuminates.
Bit
Monitoring limit values channel 0 ... 3
Bit 0: channel 0
Bit 1: channel 1
Bit 2: channel 2
Bit 3: channel 3
Bit 4 .. 7: reserved (0)
Values
0 = inactive (presetting)
1 = active
Comment
If the limit value has been reached (operating mode B) or fallen below/exceeded
(operating mode C, D), it is signaled in the PII (
Tab. 3/21: Monitoring limit values (channel-specific, channel 0 ... 3)
Festo P.BE-CPX-P-EA-EN en 1209NH English
Handheld
m = module number (0 ... 47)
[Monitor limits]
[Ch 0]
[Ch 1]
[Ch 2]
[Ch 3]
[Inactive]
[Active]
Tab. 3/9).