Module Parameters Cpx-P-8De-N - Festo CPX-P-8DE-N Series Description

Cpx terminal (-p) modules and connection blocks
Table of Contents

Advertisement

3. Input module CPX-P-8DE-N-...

3.3.7 Module parameters CPX-P-8DE-N..

Overview of module parameters CPX-P-8DE-N..
1)
Function number
4828 + m * 64 + 0
4828 + m * 64 + 1 ... 5
4828 + m * 64 + 6
4828 + m * 64 + 7
4828 + m * 64 + 8
4828 + m * 64 + 9
4828 + m * 64 + 10
4828 + m * 64 + 11
4828 + m * 64 + 12
4828 + m * 64 + 13
4828 + m * 64 + 14
4828 + m * 64 + 15
4828 + m * 64 + 16
4828 + m * 64 + 17
4828 + m * 64 + 18 ... 25
4828 + m * 64 + 26 ... 33
4)
-
4)
-
4)
-
1)
m = module number (counting from left to right, beginning with 0)
2)
An alteration of the parameter causes a reinitialisation of the respective channel.
3)
This parameter is only available in the extended process image (miniature switch = ON).
4)
Access is protocol-specific (
Tab. 3/18: Overview of module parameters CPX-P-8DE-N..
3-26
Bit
Module parameter
0 ... 6
Reserved
7
Monitoring parameter
0 ... 7
Reserved
0 ... 7
Operating mode input channel 0 ... 3
0 ... 3
Monitoring of limit values
0 ... 7
Monitoring short circuit
0 ... 7
Wire break monitoring
0 ... 7
Signal extension time channel 0 ... 3
0 ... 7
Signal extension time channel 4 ... 7
0 ... 7
Input debounce time channel 0 ... 3
0 ... 7
Input debounce time channel 4 ... 7
0 ... 7
Replacement value channel 0 ... 3
Replacement value channel 4 ... 7
0 ... 7
Counter configuration (channel 0 ... 3)
0 ... 7
Gate time
0 ... 7
Lower limit value
0 ... 7
Upper limit value
0 ... 7
Fail safe channel x
0 ... 7
Idle mode channel x
0 ... 7
Forcing channel x
bus node description)
Default
active
2)3)
Digital input
3)
inactive
2)
active
2)
inactive
2)
inactive
2)
2)
3 ms
2)
2)
0
2)
2)3)
positive edge;
count upwards
2)3)
1000 ms
2)3)
0
2)3)
1000
Festo P.BE-CPX-P-EA-EN en 1209NH English

Advertisement

Table of Contents
loading

Table of Contents