Festo CPX-P-8DE-N Series Description page 80

Cpx terminal (-p) modules and connection blocks
Table of Contents

Advertisement

3. Input module CPX-P-8DE-N-...
Module parameter: Operating mode of the input channel
This parameter is only available in the extended process image (miniature switch = ON).
4828 + m * 64 + 6
Function no.
Description
Specifies the operating mode for the first 4 input channels (0 .. 3) of the module.
– Operating mode A: Digital input
– Operating mode B: Counter
– Operating mode C: Frequency measurement up to 1 kHz
– Operating mode D: Frequency measurement up to 10 kHz (only possible for chan-
nel 0)
An alteration of the parameter causes an initialisation of the respective channel.
Bit
Operating mode of the input channel (input function)
Bit 1,
Values
Comment
Current counter values and frequencies are shown in the PII (byte 2 ... 9).
Inputs 4 ... 7 can be used exclusively as digital inputs according to specification EN
60947-5-6 (Namur).
Tab. 3/20: Operating mode of the input channel (channel-specific, channel 0 ... 3)
3-30
0
Duct 0
3,
2
Duct 1
5,
4
Duct 2
7,
6
Duct 3
0
0
Digital input (A) (presetting)
0
1
Counter input (B)
1
0
Frequency measurement up to 1 kHz (C)
1
1
Channel 0 only: Frequency measurement
up to 10 kHz (D)
m = Module number (0 ... 47)
Festo P.BE-CPX-P-EA-EN en 1209NH English
Handheld
[Input function]
[Ch 0]
[Ch 1]
[Ch 2]
[Ch 3]
[Digital input]
[Counter]
[Frequency 1 kHz]
[Frequency 10 kHz]