3. Input module CPX-P-8DE-N-...
Module error LED
LED (red)
Process
ON
OFF
LED not illu-
minated
error-
specific
LED flashes
ON
OFF
LED
illuminated
1)
Details
section 3.3.9.
Tab. 3/41: Module error LED
Channel error LED
LED (red)
Process
ON
OFF
LED not illu-
minated
error-
specific
LED flashes
ON
OFF
LED
illuminated
Tab. 3/42: Channel error LED
3-52
Status
Trouble-free operation
Minor error
(e.g. parameterisation er-
ror)
Serious error
(e.g module/channel
failed)
Status
Trouble-free operation
Wire break
Error on the corresponding
channel (e.g. short circuit
or limit value reached)
Significance / error handling
None
Check the parameterisation measures
conducted and, if necessary, conduct
the parameterisation process again
with the correct parameters
Check the supply voltage; power
Off/On necessary; repeat occurrence
means servicing required
Significance / error handling
None
Eliminate wire break
Eliminate error on the corresponding
channel; check connected field device
if necessary