The product labelling and the Data Matrix Code are printed on the housings of the modules. Scanning the Data Matrix Code with an appropriate device opens the Festo Internet page with documents appropriate for the product. Alternatively, the Product Key (11-digit alphanumeric code on the product labelling) can be entered in the search field è...
The qualified personnel have skills and experience in dealing with electrical (open-loop) control technology. Additional information – Contact the regional Festo contact if you have technical problems è www.festo.com. – Accessories and spare parts è www.festo.com/catalogue. Festo — CPX-AP-A-12DI4DO-M12-5P — 2022-07...
After the short circuit or the overload has been cleared, the power supply is not switched on again until after the output is reset. The electronic fuse of the module is a slow-blow type. Electrical consumers with a temporarily higher current requirement can therefore also be connected. Festo — CPX-AP-A-12DI4DO-M12-5P — 2022-07...
Connected digital output load exceeds allowed power con- (16843020) load output signal sumption. – Check the connected load for proper func- Remedy tion, especially current consumption. – Check cable. – The output must be reset after the fault is resolved. – Festo — CPX-AP-A-12DI4DO-M12-5P — 2022-07...
Page 11
– Check power supply. Remedy Diag- Error nostic status 08 | 01 | 0124 AP master lost No communication with AP master possible. (134283556) – Restart AP master. Remedy – Check communication cable (AP) Diag- Error nostic status Festo — CPX-AP-A-12DI4DO-M12-5P — 2022-07...
Page 12
State Emergency system is in maintenance mode. No I/O function is avail- Operation able. – Restart system Remedy – Update firmware to latest version – Contact Festo service Diag- Error nostic status Tab. 9: Diagnostic messages Festo — CPX-AP-A-12DI4DO-M12-5P — 2022-07...
PS red light Module ramp-up not yet completed. – System communication not yet initial- ised. flashing red 2 Hz Module identification (service function) – flashing green 2 Hz Tab. 10: LED module diagnostics [MD] Festo — CPX-AP-A-12DI4DO-M12-5P — 2022-07...
Page 14
Tab. 12: LED status of output Diagnostics of output LED (red) Meaning Remedy Short circuit/overload at output Check the connected actuators, elimi- nate short circuit/overload. Illuminated No channel error at output – Tab. 13: LED diagnostics of output Festo — CPX-AP-A-12DI4DO-M12-5P — 2022-07...
By the use of SELV/PELV circuits tion against direct and indirect contact (Safe extra-low voltage/Protected extra-low voltage) in accordance with IEC 60204-1 and IEC 60364-4-41) Electromagnetic compatibility See declaration of conformity è www.festo.com Mounting position Tab. 15: General technical data Festo — CPX-AP-A-12DI4DO-M12-5P — 2022-07...
Page 16
[V DC] 24 ± 25% Intrinsic current consump- [mA] Typically 5 tion at nominal operating voltage 24 V from PL £ 17.7 Diagnostics message, under- [V DC] voltage in load supply PL Tab. 16: Power supply Festo — CPX-AP-A-12DI4DO-M12-5P — 2022-07...
Page 17
0 V SEN external and 0 V SEN internal Sensor power supply short circuit protection Short-circuit protection Electronic > 1.8 Trigger level Characteristic Slow-blowing Response after end of over- Automatic recovery load Tab. 17: Digital inputs Festo — CPX-AP-A-12DI4DO-M12-5P — 2022-07...
Page 18
Response after end of over- No automatic recovery load Output delay with resistive load Signal change from 0 to 1 [µs] . 200 Signal change from 1 to 0 [µs] . 200 Tab. 18: Digital outputs Festo — CPX-AP-A-12DI4DO-M12-5P — 2022-07...