Eaton easyE4 Manual page 707

Hide thumbs Also See for easyE4:
Table of Contents

Advertisement

Electromagnetic compatibility (EMC)
Overvoltage category/degree of pollution
Electrostatic discharge (ESD)
The contact discharge value for all EASY-E4-..-....1P devices with push in
terminals is 6 kV.
Electromagnetic fields (RFI)
Radio interference suppression In accordance with EN
Burst
Power pulses (Surge)
easyE4 10/19 MN050009 EN www.eaton.com
Air discharge
Contact discharge Version
EASY-E4-UC-12RC1 01
from 02 6 kV
EASY-E4-UC-12RCX1 01
from 02 6 kV
EASY-E4-DC-12TC1 01
from 02 6 kV
EASY-E4-DC-12TCX1 01
from 02 6 kV
EASY-E4-AC-12RC1 from 01 6 kV
EASY-E4-AC-12RCX1 from 01 6 kV
EASY-E4-UC-8RE1 01
02
03
EASY-E4-UC-16RE1 01
02
from 03 6 kV
EASY-E4-DC-4PE1 from 01 6 kV
EASY-E4-DC-6AE1 01
02
from 03 6 kV
EASY-E4-DC-8TE1 01
02
from 03 6 kV
EASY-E4-DC-16TE1 01
02
from 03 6 kV
EASY-E4-AC-8RE1 from 01 6 kV
EASY-E4-AC-16RE1 from 01 6 kV
according to IEC EN 61000-4-
3
61000-6-3
according to IEC/EN 61000-
4-4
according to IEC/EN 61000-
A.3 Technical data
III/2
according to IEC EN 61000-4-2
8 kV
4 kV
4 kV
4 kV
4 kV
4 kV
4 kV
6 kV
4 kV
4 kV
4 kV
4 kV
4 kV
4 kV
4 kV
4 kV
0.8 - 1.0 GHz: 10 V/m
1.4 - 2 GHz: 3 V/m
2.0 - 2.7 GHz: 1 V/m
Class B
Supply cables: 2 kV
Signal cables: 2 kV
1 kV (supply cables, symmetrical)