Eaton easyE4 Manual page 359

Hide thumbs Also See for easyE4:
Table of Contents

Advertisement

Operators
2)
nN - NET marker bit
NET station n
ID: Diagnostic alarm
LE - Output backlight
P device buttons
I - Bit input
Q - Bit output
Q - Bit output of a FB
2) Only on projects with ≥ 2 base devices on NET
Operating mode
Description
Operating mode
UNP
The manipulated variable is output as a
unipolar 12-bit value. .
BIP
The manipulated variable is output as a
bipolar 13-bit value.
Function block outputs
Description
(Bit)
LI
1: if the value range of the medium-voltage is
exceeded.
(DWord)
QV
Manipulated variable
QP
Proportional component of the manipulated vari-
able
Can be used for diagnostic purposes
QI
Integral component of the manipulated variable
Can be used for diagnostic purposes
QD
Differential component of the manipulated vari-
able
Can be used for diagnostic purposes
Assigning operands
You can assign the following operands to the function block outputs that are numeric
outputs:
Assigning operands
MB, MD, MW - Markers
NB, NW, ND - NET markers
NET stations n
QA - Analog output
I - Value input of a FB
2) Only on projects with ≥ 2 base devices on NET
You can assign the following operands to the function block outputs that are bit outputs:
easyE4 10/19 MN050009 EN www.eaton.com
Bit inputs
x
x
x
x
x
x
x
Value outputs
x
2)
x
x
x
6. Function blocks
6.1 Manufacturer function blocks
Note
Value range: 0 ... 4095
Value range: -4096 ... +4095
Note
Integer value range
for operating mode UNP: 0...+4095 (12 Bit)
for operating mode BIP: -4096...+4095 (13
Bit)
355

Advertisement

Table of Contents
loading

Table of Contents