Eaton easyE4 Manual page 237

Hide thumbs Also See for easyE4:
Table of Contents

Advertisement

6. Function blocks
6.1 Manufacturer function blocks
Setting time range parameters in which the on phase is from the beginning of the
month to the end of the month (whole month(s)):
First channel ON: -- 04 --, OFF: -- 10 -- means:
This year time switch will switch on on April 01st at 00:00 and after the OFF month
elapses will switch off on November 01st at 00:00. The parameters are set in one chan-
nel. Compare this to → "Example 2: Select month ranges", page 234 for this time range
found below.
Setting time range parameters in which the on phase is from the beginning of the
day to the end of the day for each month in each year (whole day(s)):
First channel ON: 02 -- --, OFF: 25 -- -- means:
The year time switch should switch on at 00:00 h on day 2 of each month, and switch
off when the OFF day has elapsed at 00:00 h on day 26. The parameters are set in one
channel. Refer to the → "Example 3: Select day ranges", page 235 below for this time
range.
Setting time range parameters in which the on phase is from the beginning of the
day to the end of the day for specified months and years year (day, month, year):
First channel ON: 02 04 25; OFF: 25 09 25 means:
The year time switch will switch on on 04/02/2015 at 00:00:01 and off on 09/26/2029 at
00:00:00. Outside of the configured time range, the time switch will remain off.
Setting overlapping time ranges:
Refer to the → "Example 7: Overlapping ranges", page 237 below for these time ranges.
In these cases, a time cannot be configured for switching, and switching will always
occur for the entire day, from 00:00 to 24:00. This is a set configuration that cannot be
modified at runtime.
easyE4 10/19 MN050009 EN www.eaton.com
233

Advertisement

Table of Contents
loading

Table of Contents