1.10 Engineering

1.10.1 Length of input cables

The easyE4 series makes it possible to combine multiple voltage variants. Each easyE4
base device can be wired with up to 11 EASY-E4-...-...E1(P) expansions with different
power supplies.
Severe interference can cause a signal 1 on the inputs without a proper signal being
applied. Observe therefore the following maximum cable lengths:
Base device inputs I1–I6
40 m for AC supply voltages; 100 m for DC supply voltages
l
Base device inputs I7–I8
100 m for AC supply voltages; 100 m for DC supply voltages
l
Expansion device inputs
40 m for AC supply voltages; 100 m for DC supply voltages
l
In addition, the following applies to base devices and expansion devices:
With longer cables, connect a diode (e.g. 1N4007) with a minimum reverse voltage of 1
kV and a let-through current of 1 A in series to the device inputs. Ensure that the diode
is pointing to the input; otherwise the device will not be able to detect the 1 state.