11.4 Functionality of the NET faulty
NOTICE
You can make a visual check the functionality of the NET by means of
the NET LED and in the circuit diagram via diagnostics bit ID01-ID08.
Checking the functionality of the NET using the NET LED
Status of the
Description
NET LED
Off
NET not operational, fault in configuration
Continuous light
NET station fault - possible causes:
Net is initialized and at least one station has not been detected. Check the plug-in
l
connections.
You have modified the NET ID or baud rate for at least one station after the con-
l
figuration has been completed. Change the configuration.
You have deleted the program on a NET station and thus also its NET configuration.
l
Reconfigure the NET via station 1.
You have expanded an existing NET station and replaced it with a new device
l
which cannot be assigned parameters.
Flashing
NET operating fault-free