Operation upon error occurring
The product operating status and LED status will differ depending on the type of error generated.
For error types, see the following page.
Page 220 List of Error Codes
Operation upon error detection setting
Set operation settings upon error detection.
MELIPC operation upon error detection setting
Configure the operation of this product when a problem is detected by using "MELIPC operation upon error detection setting"
of "RAS Setting".
Window
[Basic Parameter]  [RAS Setting]  [MELIPC Operation Setting at Error Detected]
Displayed items
Item
MELIPC temperature error
*2
Windows part stop
*1 If "Shutdown" is selected, the operation upon error detection is the same as when the SHUTDOWN switch is pressed. ( Page 120
MELIPC Shutdown Function)
*2 If the Windows part continuously restarts, a window to select whether to start Windows in safe mode is displayed.
*3 If "Do not restart" is selected, the error code is recorded in the event history at error detection, the MAIN ERR LED is lit, and the WIN
RDY LED is off.
If "Restart" is selected, the Windows part is restarted at error detection, and an event stating it restarted automatically is saved in the
event history.
For details on the internal configuration of this product (Windows part and VxWorks part), refer to the following
manual.
MELIPC MI5000 Series User's Manual (Startup)
Precautions
■Automatic restart at a Windows system error
If Windows automatic restart is enabled, and 'Restart' is selected for when the Windows part stops, this product may restart
repeatedly. If 'Restart' is selected, disable Windows automatic restart.
Windows Start  [Windows System Tools]  [Control Panel]  [System and Security]  [System]  [Advanced system
settings]  [Advanced]  [Startup and Recovery]  [Settings]  [System failure]  [Automatically restart]
■If the MELIPC temperature error settings are "Shut down"
The product may not shut down if MI Configurator or programs that make file accesses are operating, or depending on the
status of Windows.
8 DIAGNOSTIC AND MAINTENANCE FUNCTIONS
96
8.1 Self Diagnostics Function
Description
*1
Set the device operation upon detection of a Main module temperature
error.
If "Shutdown" is set, the VxWorks part and Windows part shut down when
an error is detected.
Set operation of the Windows part when a stop state is detected due to a
Windows blue screen including timeout detection from the Windows part
system watchdog timer or other issue.
Setting range
• Shut down
• Do not shut down
(Default: Shutdown)
*3
• Do not restart
• Restart
(Default: Do not restart)