Timeout occurs
Check the following items.
Check item
Is the link scan time setting of the master station too short, or is the link scan
time setting disabled (0 ms)?
Check the troubleshooting in the following section as well.
Page 213 Transmission status repeats disconnection and reconnection
Slow link scan time
Refer to the following troubleshooting items.
Page 210 Stations repeatedly disconnect and reconnect
Slow access to the product
Check the following items.
Check item
Are any of the following functions being run?
• Access from MI Configurator
• Access using the local network
Are there any delays in response, error responses, or no responses with
functions using the Ethernet port (CH1) such as FTP, socket communications,
or SLMP?
On the same circuit, is CC-Link IE Field Network Basic running at the same
time on a different network address?
Are communications with other Ethernet devices being carried out on the
same line?
Master station cyclic transmission is stopped
Check the following items.
Check item
Is the slave station transmission status normal?
Start data assurance of link devices.
The date and time of the Windows part and VxWorks part are
different
Check the following items.
Check item
Is "Do not use" configured for "Clock data synchronization"?
• [Basic Parameter]  [Operation Related Setting]  [Time Related Setting]
 [Clock Data Synchronization]
Are the time zone settings of the Windows part and VxWorks part different?
Are the daylight saving time settings of the Windows part and VxWorks part
different?
Is "Set time automatically" of Windows set to "ON".
• [Settings]  [Time & language]  [Date and time]  [Set time automatically]
APPX
214
Appendix 1 Troubleshooting by Symptom
Corrective action
• Lengthen the link scan time of the master station.
• If the link scan time setting is disabled, make it enable (1ms or more).
Corrective action
Stop the function. Alternatively, review settings, such as by increasing the
interval between executions of these functions, decreasing their frequency, or
reducing the range.
Stop the function. Alternatively, review settings, such as by increasing the
interval between executions of these functions or decreasing their frequency.
Separate the network to a separate circuit and create a CC-Link IE Field
Network Basic.
Separate the network into a CC-Link IE Field Network Basic network and a
different Ethernet device network, then run.
Corrective action
• If there are disconnected slave stations, handle as per the error details.
• If there are no disconnected slave stations, this may indicate a problem with
a device other than the device set as the master station, so check the
network connections.
• Always end data assurance of link devices by the task that started data
assurance of link devices.
• Either turn the power supply of this product OFF to ON or reset this product.
Corrective action
Set "Use" for "Clock data synchronization"?
Use the same time zone setting for the Windows part and VxWorks part.
Use the same daylight saving time settings for the Windows part and VxWorks
part.
Set "Set time automatically" to "OFF".