Download Print this page

Mitsubishi Electric MELIPC MI5000 Series User Manual page 228

Hide thumbs Also See for MELIPC MI5000 Series:

Advertisement

Error code
3E41H
3E42H
3E46H
3E47H
3E4BH
3E4CH
3E4EH
APPX
226
Appendix 2 List of Error Codes
Error name
System WDT error
System WDT error
Hardware failure
Hardware failure
Hardware failure
Hardware failure
Hardware failure
Description
• The system watchdog timer managed by
the system detected an error.
Alternatively, an error occurred in system
software.
• The system WDT monitoring time is
short.
• Tasks with the higher CPU usage rate is
in operation.
• A program causing an error in the
memory or stack was executed.
• The operation that increase the CPU
usage rate of the system task (writing
parameter) was performed.
• The station on which the station-based
block data assurance setting is enabled
on the network has been accessed when
the stop error occurred.
• MELIPC is uncontrollable or damaged
(malfunction from noise, or hardware
fault).
• BIOS settings screen started.
The system watchdog timer managed by
the system detected an error. Alternatively,
an error occurred in system software.
• The system WDT monitoring time is
short.
• Tasks with the higher CPU usage rate is
in operation.
• A program causing an error in the
memory or stack was executed.
• The operation that increase the CPU
usage rate of the system task (writing
parameter) was performed.
• The station on which the station-based
block data assurance setting is enabled
on the network has been accessed when
the stop error occurred.
• An error was detected in the memory.
• MELIPC is uncontrollable or damaged
(malfunction from noise, or hardware
fault).
A hardware failure was detected.
A hardware failure was detected.
A hardware failure was detected.
A hardware failure was detected.
A hardware failure was detected.
Corrective action
• Reset the system. Lower the CPU
utilization of tasks with high CPU
utilization. Alternatively, do not run them.
• Review the user program.
• Set a sufficiently long system WDT
monitoring time after consideration of the
CPU utilization of the system tasks.
• Review the user program to prevent the
station on which the station-based block
data assurance setting is enabled from
being accessed when the stop error
occurred.
• Take measures to reduce noise.
• Confirm that the ambient environment is
within general specifications.
• When starting this product, ensure that
the BIOS settings screen does not start.
If the same error is displayed again, this
may indicate a hardware fault. Consult your
local Mitsubishi representative.
• Reset the system.
• Lower the CPU usage rate of tasks with
the higher rate, or make them inactivated.
• Review the user program.
• Set a sufficiently long system WDT
monitoring time after consideration of the
CPU utilization of the system tasks.
• Review the user program to prevent the
station on which the station-based block
data assurance setting is enabled from
being accessed when the stop error
occurred.
• Take measures to reduce noise.
• Confirm that the ambient environment is
within general specifications.
If the same error is displayed again, this
may indicate a hardware fault. Consult your
local Mitsubishi representative.
• Take measures to reduce noise.
• Reset the system. If the same error is
displayed again, this may indicate a
hardware fault. Consult your local
Mitsubishi representative.
• Take measures to reduce noise.
• Reset the system. If the same error is
displayed again, this may indicate a
hardware fault. Consult your local
Mitsubishi representative.
• Take measures to reduce noise.
• Reset the system. If the same error is
displayed again, this may indicate a
hardware fault. Consult your local
Mitsubishi representative.
• Take measures to reduce noise.
• Reset the system. If the same error is
displayed again, this may indicate a
hardware fault. Consult your local
Mitsubishi representative.
• Take measures to reduce noise.
• Reset the system. If the same error is
displayed again, this may indicate a
hardware fault. Consult your local
Mitsubishi representative.

Advertisement

loading

This manual is also suitable for: