Advance processing during a forced restart
VxWorks part processing that was registered by the user in advance can be executed before the Windows part is forced to
restart.
Advance processing is registered using the C Controller module dedicated function (CCPU_EntryWinResetFunc).
■Function list
Function name
CCPU_EntryWinResetFunc
For details on the C Controller module dedicated functions, refer to the following manual.
MELIPC MI5000 Series Programming Manual (VxWorks)
Precautions
■Windows part forced restart permission
Excluding forced restarts from a switch operation, it is necessary to allow forced restarts of the Windows part using MI
Configurator.
[Basic Parameters]  [Operation Related Settings]  [Remote Reset Setting]  [Windows part forced restart]
■Considerations before forcing a restart of the Windows part
If Windows is forced to restart during operation of a user program, the files of the Windows part may be corrupted. Before
forcing a reset of the Windows part, always take measures to prevent file corruption, such as stopping user programs.
Furthermore, enable the Unified Write Filter of this product to protect the Windows part system files. (MELIPC MI5000
Series User's Manual (Startup))
■Considerations after forcing a restart of the Windows part
If the Windows part was forced to restart, the shared memory of the OS linking function is not in the same status as when the
power supply of this product is turned OFF and ON. To clear the shared memory, turn the power supply of this product OFF
and ON or reset this product.
■When user programs of the VxWorks part and Windows part are linked
When user programs of the Windows part and VxWorks part are linked using virtual Ethernet or shared memory, user
applications of the VxWorks part may be affected if the Windows part is forced to restart. Therefore, stop linked processing
and take other measures to ensure that the user applications of the VxWorks part are not affected by a forced restart of the
Windows part.
■Considerations after running the shutdown function
The Windows forced-restart function cannot be run when the shutdown function has set this product in a state in which the
power supply can be turned OFF. Switch the power supply of this product OFF to ON.
■Functions that cannot be used for advance processing of Windows part forced-restart
Do not use the following functions for advance processing of the Windows part forced-restart registered by the user. The
Windows part forced-restart may not be completed.
• CCPU_MELIPCShutdown
• CCPU_WinReset
If user processing that uses the above-mentioned functions was registered, and a Windows part forced-restart was run, switch
the power supply of this product OFF and ON, and then change the registered processing.
8 DIAGNOSTIC AND MAINTENANCE FUNCTIONS
124
8.9 Individual Reset Function
Description
Registers a routine to be called before the Windows forced-restart function of the individual reset function is executed.