Supported commands
This section shows the SLMP commands supported by this product.
For details on SLMP commands, refer to the following manual.
SLMP Reference Manual
Item
Type
Operation
Device
Read
Write
Read Random
Write Random
Read Block
Write Block
Remote
Remote Run
Control
Remote Stop
Remote Reset
Read Type Name
File
Read Directory/
File
Search Directory/
File
New File
Delete File
Copy File
Change File State
Change File Date
Open File
Read File
Write File
Close File
*1 The  section of the command depends on the device to be specified.
For details, refer to the following manual.
SLMP Reference Manual
*
Comman
Subcommands
1
d
0401
• 001
• 003
• 000
• 002
1401
• 001
• 003
• 000
• 002
0403
• 000
• 002
1402
• 001
• 003
• 000
• 002
0406
• 000
• 002
1406
• 000
• 002
1001
0000
1002
0000
1006
0000
0101
0000
1810
0040
1811
0040
1820
0040
1822
0040
1824
0040
1825
0040
1826
0040
1827
0040
1828
0000
1829
0000
182A
0000
Description
Reads values from bit devices (consecutive device number) in 1-point units.
• Reads values from bit devices (consecutive device number) in 16-point units.
• Reads values from word devices (consecutive device number) in 1-word units.
Writes values to bit devices (consecutive device number) in 1-point units.
• Writes values to bit devices (consecutive device number) in 16-point units.
• Writes values to word devices (consecutive device number) in 1-word units.
Reads values from word devices in 1-word units or 2-word units by specifying
device number. Nonconsecutive device numbers can be specified.
Writes values to bit devices in 1-point units by specifying device number.
Nonconsecutive device numbers can be specified.
• Writes values to bit devices in 16-point units by specifying device number.
Nonconsecutive device numbers can be specified.
• Writes values to word devices in 1-word units or 2-word units by specifying
device number. Nonconsecutive device numbers can be specified.
Reads data by specifying multiple blocks as regarding one block as n-point of
word devices or bit devices (1-point is 16-bit). Nonconsecutive device numbers
can be specified.
Writes data by specifying multiple blocks as regarding one block as n-point of word
devices or bit devices (1-point is 16-bit). Nonconsecutive device numbers can be
specified.
Performs remote RUN to the access target module.
Performs remote STOP to the access target module.
Performs remote RESET to the access target module.
Reads model and model code of the access target module.
Reads information list of the file.
Reads fine number and existence of the specified file.
Reserves the storage area in the specified file.
Deletes files.
Copies the specified file.
Changes the file attribute.
Changes the file creation date.
Locks the file in order that the file content is not changed form other devices.
Reads the content of a file.
Writes content to a file.
Unlocks a file with open processing.
4 SLMP FUNCTION
4.1 SLMP Server Functions
4
37

Advertisement

loading

This manual is also suitable for:

Melipc mi5122-vw