Error code
Error name
D0C5H
CC-Link IE Field Network function
related errors
D0D0H
CC-Link IE Field Network function
related errors
D200H
CC-Link IE Field Network function
related errors
D202H
CC-Link IE Field Network function
related errors
D203H
CC-Link IE Field Network function
related errors
D204H
CC-Link IE Field Network function
related errors
D205H
CC-Link IE Field Network function
related errors
D206H
CC-Link IE Field Network function
related errors
D208H
CC-Link IE Field Network function
related errors
D209H to D20AH
CC-Link IE Field Network function
related errors
D20BH to D20CH
CC-Link IE Field Network function
related errors
D20DH
CC-Link IE Field Network function
related errors
D20EH
CC-Link IE Field Network function
related errors
D20FH
CC-Link IE Field Network function
related errors
D210H
CC-Link IE Field Network function
related errors
D211H
CC-Link IE Field Network function
related errors
D212H
CC-Link IE Field Network function
related errors
D213H
CC-Link IE Field Network function
related errors
D214H
CC-Link IE Field Network function
related errors
Description
During temporary error disabled station
settings clear specification processing,
temporary error disabled station settings
clear specification was performed again.
Other station's station No. settings were not
correctly carried out.
Duplicate received in transient
transmission.
Transmission buffer full.
Error in the transient transmission data
read/write address.
Error in the transient transmission network
No.
Error in the transient transmission target
station No.
Error in the transient transmission network
No.
Error in the transient transmission network
No.
Error in the transient transmission target
station No.
No master station when setting specified
master station in transient transmission.
In transient data transmission, there was a
transmit end wait time out.
Error in the transient transmission header
information.
Commands that cannot be requested
through transient transmission all station
specification or group specification were run
as all station specification or group
specification.
Error in the transient transmission target
station No.
Transient transmission carried out when
own station's station number is
unconfirmed.
Transient transmission failed.
Error in the transient transmission
command.
Error in the transient transmission data
length.
Corrective action
Wait some time before again carrying out
temporary error disabled station settings
clear specification.
Wait some time before again specifying
other station's station No.
• In engineering tools CC-Link IE Field
diagnoses, check the network status, and
take measures.
• Check that there are no faults with the
request source cable or a switching hub
connections.
• Lower the transient transmission usage
frequency, and then perform again.
• Check that there are no faults with the
request source cable or a switching hub
connections.
Read data at the transient request source,
correct the write address, and run again.
Correct the network number at the transient
request source, and run again.
Correct the target station No. at the
transient request source, and run again.
Correct the network number at the transient
request source, and run again.
Correct the network number at the transient
request source, and run again.
Correct the target station No. at the
transient request source, and run again.
Correct the target station No. at the
transient request source, and run again.
• In engineering tools CC-Link IE Field
diagnoses, check the network status, and
take measures.
• If an error is detected in own station,
target station, or relay, then confirm the
source of the error, and take measures.
• Lower the transient transmission usage
frequency, and then perform again.
• Check that there are no faults with the
request source cable or a switching hub
connections.
Correct the header information at the
transient request source, and run again.
Check commands that can be requested at
the transient request source to all stations
or to groups, and run again.
Correct the header information at the
transient request source, and run again.
Set own station's station number, and run
transient transmission again.
• Check that there are no faults with the
request source cable or a switching hub
connections.
• Lower the transient transmission usage
frequency, and then perform again.
Correct the request command at the
transient request source, and run again.
Correct the data length at the transient
request source, and run again.