Download Print this page

Mitsubishi Electric MELIPC MI5000 Series User Manual page 254

Hide thumbs Also See for MELIPC MI5000 Series:

Advertisement

Error code
D90BH
D90CH
D90DH
D912H
D913H to D917H
DA00H to DA01H
DA10H to DA16H
DA17H
DA19H
APPX
252
Appendix 2 List of Error Codes
Error name
CC-Link IE Field Network function
related errors
CC-Link IE Field Network function
related errors
CC-Link IE Field Network function
related errors
CC-Link IE Field Network function
related errors
CC-Link IE Field Network function
related errors
CC-Link IE Field Network function
related errors
CC-Link IE Field Network function
related errors
CC-Link IE Field Network function
related errors
CC-Link IE Field Network function
related errors
Description
The number of stations communicating on
the network is outside the specified range.
Error in communications test target station
specifications.
During cable test run, this was re-run.
Transient transmission failed.
MELIPC error detected.
MELIPC error detected.
MELIPC error detected.
MELIPC error detected.
MELIPC error detected.
Corrective action
• In CC-Link IE Field diagnosis of an
engineering tool, check the network
status, and then take measures.
• If there are in excess of 120 slave
stations on 1 network, then reduce this to
120 or less.
• Correct "Communications destination
settings" of the communications test, and
run again.
• "Communications destination settings"
cannot be run for the own station and
relay transmission stations.
After cable test has completed, run again.
• Lower the transient transmission usage
frequency, and then perform again.
• Check that there are no faults with the
cable or a switching hub connections.
Consult your local Mitsubishi
representative.
Consult your local Mitsubishi
representative.
Consult your local Mitsubishi
representative.
Consult your local Mitsubishi
representative.
Consult your local Mitsubishi
representative.

Advertisement

loading

This manual is also suitable for:

Melipc mi5122-vw