Station type fixed mode settings
Module list
18 APPRICATION PARAMETERS
196
18.2 Network Configuration Settings
Description
Set the station type for other than the master station.
Ensure that the station type matches the module station type actually
connected to the network.
Set RX and RY assignment.
Set RX and RY as 16 point unit (start: 0H, end: FH).
To set the average of point numbers, and to set these equally, do so
from [CC IE Field configuration]  [Equal assignment] or [Same point
assignment].
Set RWw and RWr assignments as 4 point units.
To set the average of point numbers, and to set these equally, do so
from [CC IE Field configuration]  [Equal assignment] or [Same point
assignment].
Set when setting slave stations as reserved stations or error disabled
stations.
• Not set: connect slave station to the network.
• Reserved: reserve slave stations in parameters for future
extensibility. Use of a reserved station means that even if a slave
station is added (reserve station deleted), link device assignment will
not change, meaning program change is not necessary. In actual
networks, slave stations do not need to be connected.
• Error Invalid Station: ensure that slave stations in data link are not
detected as faulty stations in the master station.
If "RJ71GF11-T2(SR)" or "RJ72GF15-T2(SR)" have been set in
network configuration, then stations set for pairing will be displayed.
Set whether to synchronize slave stations using the CC-Link IE Field
Network synchronous communication function.
Enter an arbitrary device name.
The input device name is displayed in the CC-Link IE Field Network
diagnostics "Network status".
However, in additional remote device station modules, CC-Link IE Field
Network diagnostics does not display the device name even if this is
input.
This displays the content input into "Comment 1" in the "Property"
screen selected by right-clicking the unit either in the station list or the
network configuration diagram.
Set the slave station type fixed mode. This can only be set if the slave
station supports station fixed mode.
Displays the slave station list.
From the "Unit List", drag and drop modules to the "Station list" or
"Network configuration diagram" to set slave station information in the
master station.
Setting range
Parameter
No.
• Local Station
A044H
• Intelligent Device
Station
• Remote Device Station
• Remote I/O Station
(Depends on configured
module. )
■Points
A041H
• Local station, intelligent
device station: 16 to
2048
• Remote device station:
16 to 128
• Remote I/O station: 16
to 64
(Depends on configured
module. )
■Device number
• 0H to 3FFFH
(Depends on configured
module. )
■Points
A041H
• Local station: 4 to 256
• Intelligent device
station: 4 to 1024
• Remote device station:
4 to 64
• Remote I/O station:
Setting disabled
(Depends on configured
module. )
■Device number
• 0H to 1FFFH
(Depends on configured
module. )
• Not set
A001H
• Reserved
A002H
• Error Invalid Station
(Default: No setting)
• Asynchronous
A045H
• Synchronous
(Default: Asynchronous)
8 characters or less
A011H
(Default: Blank)
32 characters or less
A011H
(Default: Blank)
(Depends on configured module. )