■CC-Link IEF Basic setting
Item
CC-Link IEF Basic usage enabling
Network configuration settings
Refresh Setting
Link Scan Time
Settings
Group No. 1
Group No. 2
Group No. 3
Group No. 4
Output setting at MELIPC STOP
*1 When '0' is specified, the next link scan starts immediately right after the previous one is completed. (Page 83 Link scan operation)
■External device configuration
Item
External device configuration
17 BASIC PARAMETERS
174
17.1 Basic Parameter List
Description
Set to "Use" or "Do not use" CC-Link IE Field Network Basic.
Configure settings in order to carry out cyclic transmission.
Set the slave station number, exclusive station number, IP address,
and subnet mask, etc.
Furthermore, when setting CC-Link IE Field Network Basic, it is
necessary to set the network configuration.
Configure the transfer range between the CC-Link IE Field Network
Basic link devices and the MELIPC devices.
Configure the link scan time setting.
The link scan time is retained in the interval configured for each group
number.
However, when the actual link scan time is longer than the setting,
operation follows link scan time. Furthermore, this is not an item to
keep the transmission delay time constant.
Configure the link scan time of Group No. 1.
Configure the link scan time of Group No. 2.
Configure the link scan time of Group No. 3.
Configure the link scan time of Group No. 4.
Set whether to retain or clear the output of cyclic data when the
MELIPC enters a STOP condition.
Description
Configure for external device with which to communicate.
Setting range
parameter
No.
• Do not use
7920H
• Use
(Default: Do not use)
Page 177 Network
7A00H
Configuration Settings
7A02H
Page 182 Refresh
7420H
Setting
7A02H
0 to 10,000 [ms](1 ms
*1
units)
(Default: 100 ms)
• Retention
7921H
• Clear
(Default: Retain)
Setting range
parameter
No.
Page 183 External
A031H
Device Configuration

Advertisement