Download Print this page

Mitsubishi Electric MELIPC MI5000 Series User Manual page 105

Hide thumbs Also See for MELIPC MI5000 Series:

Advertisement

Error clear function
This function clears all continuation errors on the product at once.
For details on error codes, refer to the following.
Page 220 List of Error Codes
How to clear errors
Use one of the following methods to clear errors.
• MI Configurator
• C Controller module dedicated function
Precautions
• Since the function clears all continuation errors at once, error codes that should not yet be cleared may be cleared.
• Running the error clear function does not remove the cleared errors from the event history.
■MI Configurator
Use MELIPC diagnosis.
[Diagnostics]  [MELIPC Diagnostics]
■C Controller module dedicated function
Use the C Controller module dedicated function (CCPU_ClearError).
This section shows the procedure to clear errors by a user program.
1.
Execute the C Controller module dedicated function (CCPU_GetErrInfo).
Acquire information of errors that occurred on this product.
2.
Clear the cause of continuation errors detected by this product.
3.
Execute the C Controller module dedicated function (CCPU_ClearError).
Continuation errors occurring on this product are cleared.
• Function list
Function name
CCPU_ClearError
CCPU_GetErrInfo
For details on the C Controller module dedicated functions, refer to the following manual.
MELIPC MI5000 Series Programming Manual (VxWorks)
Description
Clears the continuation errors of the MELIPC.
Acquires error information of a MELIPC.
8 DIAGNOSTIC AND MAINTENANCE FUNCTIONS