Error code
D62AH
D62BH
D63DH
D63EH
D641H
D701H
D70BH
D720H
D721H
D722H
D723H
D724H
D726H
APPX
250
Appendix 2 List of Error Codes
Error name
CC-Link IE Field Network function
related errors
CC-Link IE Field Network function
related errors
CC-Link IE Field Network function
related errors
CC-Link IE Field Network function
related errors
CC-Link IE Field Network function
related errors
CC-Link IE Field Network function
related errors
CC-Link IE Field Network function
related errors
CC-Link IE Field Network function
related errors
CC-Link IE Field Network function
related errors
CC-Link IE Field Network function
related errors
CC-Link IE Field Network function
related errors
CC-Link IE Field Network function
related errors
CC-Link IE Field Network function
related errors
Description
Parameter error
Parameter error
Parameter error
Parameter error
Parameter error
Without specifying target station, reserved
station temporary clear/remove and
temporary error disabled station settings/
remove requested.
Reserved station temporary clear/remove
and temporary error disabled station
settings/remove requested simultaneously.
Error in link start/stop instruction details.
During link start/stop processing, link start/
stop requested by another station.
During link start/stop processing, link start/
stop requested by own station.
During link start/stop processing, system
link start/stop requested.
Error in link start/stop station specification
details.
Error in the transient transmission request
command.
Corrective action
• In "Applicable parameters" "CC-Link IE
Field Network Parameters", rewrite to
MELIPC.
• If the error code is displayed again even
after taking an action, consult your local
Mitsubishi representative.
• In "Applicable parameters" "CC-Link IE
Field Network Parameters", rewrite to
MELIPC.
• If the error code is displayed again even
after taking an action, consult your local
Mitsubishi representative.
• In "Applicable parameters" "CC-Link IE
Field Network Parameters", rewrite to
MELIPC.
• If the error code is displayed again even
after taking an action, consult your local
Mitsubishi representative.
• In "Applicable parameters" "CC-Link IE
Field Network Parameters", rewrite to
MELIPC.
• If the error code is displayed again even
after taking an action, consult your local
Mitsubishi representative.
• In "Applicable parameters" "CC-Link IE
Field Network Parameters", rewrite to
MELIPC.
• If the error code is displayed again even
after taking an action, consult your local
Mitsubishi representative.
After specifying the station for reserved
station temporary clear/temporary error
disabled station settings (SW0010 to
SW0017), run again.
Temporary error disabled station settings/
remove with SB0010 to SB0011, and
reserved station temporary clear/remove
with SB0012 to SB0013 cannot be run
simultaneously. After turning all of SB0010
to SB0013 OFF, turn one bit from SB0010 to
SB0013 ON, to run the operation again.
Check the settings details, and stop/start
data link.
After data link stop or start processing has
completed, run again.
After data link stop or start processing has
completed, run again.
After data link stop or start processing has
completed, run again.
Check the settings details, and stop/start
data link.
Correct the request command at the
transient request station, and run again.