Download Print this page

Mitsubishi Electric MELIPC MI5000 Series User Manual page 291

Hide thumbs Also See for MELIPC MI5000 Series:

Advertisement

Buffer memory details
CC-Link IE Field Network Basic function area
The following shows the buffer memory details of the CC-Link IE Field Network Basic function area (U3E0\G0 to
U3E0\G19999).
■Control data area
Address
Name
U3E0\G4592
Group No.1 configured
link scan time
U3E0\G4593
Group No.1 configured
slave station timeout
time
U3E0\G4594
Group No.1 configured
slave station
disconnection
detection timeout
count
U3E0\G4595
System area
U3E0\G4596
Group No.2 configured
link scan time
U3E0\G4597
Group No.2 configured
slave station timeout
time
U3E0\G4598
Group No.2 configured
slave station
disconnection
detection timeout
count
U3E0\G4599
System area
U3E0\G4600
Group No.3 configured
link scan time
U3E0\G4601
Group No.3 configured
slave station timeout
time
U3E0\G4602
Group No.3 configured
slave station
disconnection
detection timeout
count
U3E0\G4603
System area
U3E0\G4604
Group No.4 configured
link scan time
U3E0\G4605
Group No.4 configured
slave station timeout
time
U3E0\G4606
Group No.4 configured
slave station
disconnection
detection timeout
count
U3E0\G4607
System area
U3E0\G4608
Total number of
connected devices
U3E0\G4609
Reserved station
specification status
Description
The link scan time during cyclic transmission configured by a C Controller module dedicated function
(CCPU_ChangeCCIEFBCycPrm function) or MI Configurator is stored. (Unit: ms)
The slave station timeout time configured by a C Controller module dedicated function
(CCPU_ChangeCCIEFBCycPrm function) or MI Configurator is stored. (Unit: ms)
The slave station disconnection detection timeout count configured by a C Controller module dedicated
function (CCPU_ChangeCCIEFBCycPrm function) or MI Configurator is stored.
The link scan time during cyclic transmission configured by a C Controller module dedicated function
(CCPU_ChangeCCIEFBCycPrm function) or MI Configurator is stored. (Unit: ms)
The slave station timeout time configured by a C Controller module dedicated function
(CCPU_ChangeCCIEFBCycPrm function) or MI Configurator is stored. (Unit: ms)
The slave station disconnection detection timeout count configured by a C Controller module dedicated
function (CCPU_ChangeCCIEFBCycPrm function) or MI Configurator is stored.
The link scan time during cyclic transmission configured by a C Controller module dedicated function
(CCPU_ChangeCCIEFBCycPrm function) or MI Configurator is stored. (Unit: ms)
The slave station timeout time configured by a C Controller module dedicated function
(CCPU_ChangeCCIEFBCycPrm function) or MI Configurator is stored. (Unit: ms)
The slave station disconnection detection timeout count configured by a C Controller module dedicated
function (CCPU_ChangeCCIEFBCycPrm function) or MI Configurator is stored.
The link scan time during cyclic transmission configured by a C Controller module dedicated function
(CCPU_ChangeCCIEFBCycPrm function) or MI Configurator is stored. (Unit: ms)
The slave station timeout time configured by a C Controller module dedicated function
(CCPU_ChangeCCIEFBCycPrm function) or MI Configurator is stored. (Unit: ms)
The slave station disconnection detection timeout count configured by a C Controller module dedicated
function (CCPU_ChangeCCIEFBCycPrm function) or MI Configurator is stored.
The total number of connected devices configured by parameters is stored.
The reserved station specification status of the slave station configured in parameters is stored.
(0: Not specified, 1: Specified)
The station numbers configured for reserved stations can be checked by 'Reserved station specification status
of each station' (U3E0\G4610 to U3E0\G4613).
■b0: Reserved station specification status
■b1 to b15: Empty (fixed to 0)
APPX
Appendix 9 List of Buffer Memory
A
289

Advertisement

loading

This manual is also suitable for:

Melipc mi5122-vw