• At input from slave station
 The slave station link device (RX, RWr) status is output to external devices.
 The slave station link device (RX, RWr) status is stored in the master station link device (RX, RWr) using link scan.
 The master station link device (RX, RWr) status is read by a user program.
• At output from master station
 The master station link device (RY, RWw) status is changed by a user program.
 The master station link device (RY, RWw) status is stored in the slave station link device (RY, RWw) using link scan.
 The slave station link device (RY, RWw) status is output to external devices.
6 CC-Link IE Field Network FUNCTION