Operating information area
The following shows the buffer memory details of the operating information area (U3E0\G20000 to U3E0\G29999).
■Control data area
Address
Name
U3E0\G20000 to
VxWorks part system
U3E0\G20001
WDT reset maximum
time
U3E0\G20002 to
Windows part system
U3E0\G20003
WDT reset maximum
time
U3E0\G20004 to
Own node IP address
U3E0\G20005
U3E0\G20006 to
System area
U3E0\G20013
U3E0\G20014 to
Subnet mask
U3E0\G20015
U3E0\G20016 to
System area
U3E0\G20017
U3E0\G20018 to
Default gateway IP
U3E0\G20019
address
U3E0\G20016 to
System area
U3E0\G20017
APPX
292
Appendix 9 List of Buffer Memory
Description
The maximum time to reset the system WDT is stored. (Unit: ms)
The IP address configured to the Ethernet port (CH1) is stored.
■G20004
• b0 to b7: Fourth octet
• b8 to b15: Third octet
■G20005
• b0 to b7: Second octet
• b8 to b15: First octet
The subnet mask configured to the Ethernet port (CH1) is stored.
■G20014
• b0 to b7: Fourth octet
• b8 to b15: Third octet
■G20015
• b0 to b7: Second octet
• b8 to b15: First octet
The default gateway configured to the Ethernet port (CH1) is stored.
■G20018
• b0 to b7: Fourth octet
• b8 to b15: Third octet
■G20019
• b0 to b7: Second octet
• b8 to b15: First octet