List of error codes
This section shows the codes for errors that occur in this product.
Codes of errors detected by the self-diagnosis function (1000H to 3FFFH)
The following table shows the codes of errors detected by the self-diagnosis function of this product.
Error code
1000H
1080H
1090H
1120H
112EH
1165H
1166H
1200H
APPX
222
Appendix 2 List of Error Codes
Error name
Power interruption
Internal storage write count exceeded
Battery error
SNTP clock setting error
Connection establishment failed
UDP/IP send failed
TCP/IP send failed
CC-Link IE Field Network function
moderate error
Description
• A momentary power failure has occurred.
• The power supply has been shut OFF.
• While turning power on, the CFast card
was inserted or removed.
The number of writes to the internal storage
(user drive and system drive) exceeded
10,000. (Number of writes > 10,000)
• Battery voltage has dropped below
specified values.
• The battery lead connector is not
inserted.
• The battery lead connector is not properly
inserted.
Time setting failed when the power supply
of this product was turned ON or this
product was reset.
A connection could not be established in the
open processing.
Data was not sent correctly with UDP/IP.
Data was not sent correctly with TCP/IP.
A moderate error has been detected in the
CC-Link IE Field Network function.
Corrective action
• Take measures to reduce noise.
• While turning power on, do not insert or
remove the CFast card.
• Reset the system. If the same error is
displayed again, this may indicate a
hardware fault. Consult your local
Mitsubishi representative.
Exchange the MELIPC main module.
• Replace the battery.
• Check the insertion of the battery lead
connector. If it is loose, securely connect
the connector.
• Check if the setting of time setting
function is correct.
• Check if the specified SNTP server is
operating normally and there is no failure
on the network accessing the SNTP
server computer.
• Check the operation of the target device.
• Check if the open processing has been
performed in the target device.
• Review the port number of the module, IP
address/port number of the target device,
opening method, and the number of
connections.
• When the firewall is set in the target
device, check if the access is permitted.
• Check if the Ethernet cable is
disconnected.
• Check and correct the external device
configuration.
• Check the settings for connection with the
target device.
• Check the operation of the target device
or switching hub.
• Since there may be congestion of packets
on the line, send data after a certain
period of time.
• Check if the connection cable is
disconnected.
• Check that there is no connection failure
with the switching hub.
• Check the settings for connection with the
target device.
• Check the operation of the target device
or switching hub.
• Since there may be congestion of packets
on the line, send data after a certain
period of time.
• Check if the connection cable is
disconnected.
• Check that there is no connection failure
with the switching hub.
Check with the generated error in the CC-
Link IE Field Network function, and remove
errors generating faults.