Download Print this page

Mitsubishi Electric MELIPC MI5000 Series User Manual page 243

Hide thumbs Also See for MELIPC MI5000 Series:

Advertisement

■CC-Link IE Field Network Basic error codes (C000H to CFFFH)
The following shows the codes for errors that occur on CC-Link IE Field Network Basic.
Error code
Error name
CFC0H
Cyclic transmission error (master
station)
CFC1H
Cyclic transmission error (master
station)
CFC8H
Cyclic transmission error (master
station)
CFC9H
Cyclic transmission error (master
station)
CFD0H
Master station error
CFD1H
Master station error
CFE0H
Cyclic transmission error (slave
station)
CFE1H
Cyclic transmission error (slave
station)
CFE8H
Cyclic transmission error (slave
station)
CFE9H
Cyclic transmission error (slave
station)
CFF0H
Slave station error
Description
Unable to execute cyclic transmission
because multiple master stations exist in
the same network address.
Unable to execute cyclic transmission
because the error occurred in cyclic
transmission.
Unable to execute cyclic transmission
because the slave station controlled by
other master station exists.
Unable to execute cyclic transmission
because the slave station of the same IP
address exists in the same network
address.
The port No. (61450) used in CC-Link IE
Field Network Basic has already been used.
Invalid value has been set in subnet mask.
The cyclic transmission was executed for
the slave station controlled by other master
station.
The unusable number of occupied stations
has been specified from master station.
There is no response from slave station.
The slave station of the same IP address
has existed in the same network address.
The error occurred in slave station.
Corrective action
Check the existence status of master
station in network.
• Take measures to reduce noise.
• If, after running this, the same error is
displayed again, consult your local
Mitsubishi representative.
• Check the existence status of master
station in network.
• Check the slave station where the error
occurred.
• Check the existence status of slave
station in network.
• Check the slave station where the error
occurred.
Check the port No. used in the external
device configuration.
Check the parameter setting.
• Check the existence status of master
station in network.
• Check the slave station where the error
occurred.
Check the number of occupied stations
setting in master station parameter
(Network Configuration Settings).
• Check the slave station disconnection
detection setting in master station
parameter (Network Configuration
Settings).
• Check the existence status of slave
station in network.
• Check the slave station which is
disconnected.
• Take measures to reduce noise.
Check the slave station where the error
occurred.
Check the slave station where the error
occurred.
APPX
Appendix 2 List of Error Codes
A
241

Advertisement

loading

This manual is also suitable for:

Melipc mi5122-vw