Error code
CF30H
CF31H
CF50H
CF51H
CF53H~CF56H
CF70H
CF71H
Link scan settings
Set the slave station disconnection detection timeout period and number of retries.
Window
Displayed items
Item
Slave station
Time-out period (10
disconnection
to 65535)
detection
Counts
settings
Slave station
disconnection
detection image
display
*1 Timeout periods and disconnect dissection counts are counted by slave station.
*2 Within the timeout period, disconnect if after the set count connection, there is no response from the slave station.
Set an adequate value for the timeout time in accordance with the actual system used. ( Page 78 If no
response from the slave station)
Error details and cause
A parameter not supported by the target device was
specified.
System error
System error
The command could not be run because another
peripheral device is processing.
System error
There was an error on the Ethernet communication route.
Timeout error
Description
Set the timeout time (ms) for slave station disconnection detection.
Set the slave station disconnection detection number of retries.
Displays an operating image during slave station disconnection detection
time. Please refer to this when setting the "timeout period".
Corrective action
Check the version of the target device.
• Check the considerations of the function that was run.
• Check the operation status and connection of target
devices.
• Check the Ethernet cable and hub connections.
• Check the Ethernet line status.
• Reset the CPU modules and target devices, and then
run the command again.
If the problem still cannot be resolved, contact the
manufacturer of the target device.
Wait and then run the command again.
• Check the considerations of the function that was run.
• Check the operation status and connection of target
devices.
• Check the Ethernet cable and hub connections.
• Check the Ethernet line status.
• Reset the CPU modules and target devices, and then
run the command again.
If the problem still cannot be resolved, contact the
manufacturer of the target device.
• Check the operation of the target device.
• Check if the connection cable is disconnected.
• Check the considerations of the function that was run.
• Check the operation of the target device.
• Since there may be congestion of packets on the line,
send data after a certain period of time.
Setting range
*1
10 to 65535
(Default: 100 ms)
*1,*2
3 times, 5 times, 10 times
(Default: 3 times)
17 BASIC PARAMETERS
17.2 Network Configuration Settings
17
181