The Hy8Relay (extended relay module) provides 8 numbered mechanical
relays. RELAY 4 through, RELAY 11 LOGIC can be accessed through the
Installer Menu. Set the number for the relay based on the information found
in Programmable User Relays: Table 7.
Wire communication cable connections between the DUAL GATE ports, at
the base of the STC, and the extended mechanical relay module. Refer to
instructions that accompany the Hy8Relay Module.
84
hysecurity.com | 800-321-9947
Performance
N.O. Input. The relay outputs a 250ms pulse and decrements
the tenant counter when the Tenant User input is activated
and IALD, then CLD, are tripped and released. This activity
signals a prepaid customer has exited the facility.
N.O. Input. The relay outputs a 250ms pulse and increments
the special counter when the SPECIAL USER input is
activated and OALD, then CLD, are tripped and released.
This activity signals a customer has entered the facility.
N.O. Input. The relay outputs a 250ms pulse and decrements
the tenant counter when the SPECIAL USER input is
activated and IALD, then CLD, are tripped and released. This
activity signals a customer has exited the facility.
HySecurity Testing Only
Output pulses five seconds after close limit is activated.
Typically used for cycle testing.
o
odule
Ption
Description
StrongArm Programming and Operations
Wire
Connection
R1 and R2, R4
through R11
TENANT USER
R1 and R2, R4
through R11
SPECIAL USER
R1 and R2, R4
through RC11
SPECIAL USER
Do not use
N/A