User Menu: Table 5 - HySecurity StrongArm 14F Programming And Operations Manual

Vehicular barrier gate operator with controller
Table of Contents

Advertisement

u
M
: t
ser
enu
User Menu
CT 0 (OFF)
0 = Timer disabled (OFF)
CLOSE TIMER
1 second to 99 seconds
HC 0 (OFF)
0 = off
HOLD TO CLOSE
1 = on
HO (OFF)
0 = off
HOLD TO OPEN
1 = on
AP 0
0 = UPS FAIL OPEN
AC LOSS
1 = UPS FAIL CLOSE
2 = AUTO OPEN
3 = NO CLOSE TIMER
RO 0 (OFF)
0 = off
RADIO OPEN/CLOSE
1 = on
BF 2 (ON 2 SEC)
0 = off
WARN BEFORE OPER
1 = warning buzzer on
throughout gate travel
2 = warning buzzer on for
2 seconds of gate travel
3 = warning buzzer on
during gate travel
64
hysecurity.com | 800-321-9947
5
aBle
Setting Options
Assign how many seconds before open gate initiates
automatic closure. Keep setting at 0 if a hardwired,
push-button control device is being used..
NOTE: CLOSE TIMER display does not appear when
HOLD TO CLOSE is set to 1.
Set to 0 to produce a gate closure when a momentary
signal is transmitted.
Set to 1 if a constant hold to close signal, such as a
push button control, is being used. A setting of 1 also
deactivates the automatic close timer and causes its
menu to disappear. The Hold to Close replaces the
Close Timer display as the User Menu entry display.
NOTE: To comply with UL 325 Type D protection,
set HC to 1. Type D UL 325 compliance means no
automatic closing device, such as a timer, loop sensor,
or similar device shall not be employed.
Similar to Hold to Close, but configures the Open
inputs for a constant-hold function.
0 = Momentary open signal
1 = Constant hold open push button required
To comply with UL 325 Type D protection, you must
set HO to 1.
This menu item only appears if the operator is DC
powered. The setting configures how the gate
functions when AC power fails. For more information,
refer to the supplemental documentation. See page
2.
A setting of zero, configures radio input for open only.
Setting 1 adds the capability for radio input to close
the gate, but only when it is fully open.
Controls the warn-before-operate buzzer and can be
configured three ways:
Set to 0: Buzzer is disabled. The buzzer will still beep
if alerts, faults, errors, or entrapment occur.
Set to 1: Buzzer beeps for 3 seconds before gate
moves and continues through entire length of travel.
Set to 2: Buzzer beeps for 3s before gate moves and
continues for 2s of travel.
Set to 3: Available on barrier operators only and
UC 4 if sensor inputs set to 1 "NOT USED". Buzzer
beeps when gate starts to move and continues
throughout gate travel.
Menu Tasks & Explanations
StrongArm Programming and Operations
STC Wire
Connections
Not applicable (N/A)
COM
Close
COM
Open
COM
Terminal #21
UPS Terminal strip 24
VDC to control box
power disconnect
switch - and +
COM
RADIO Open
Not applicable (N/A)
MX3657-01 Rev. D ©2020