Output Setting - SMC Networks EX600-SEC Series Operation Manual

Fieldbus system, ethercat compatible si unit
Table of Contents

Advertisement

•SI unit parameters (1)
Parameter
No.
(H.T. Symbol)
Generated error
Power supply
when control and
for control and
input power supply
1
input voltage
voltage goes over
monitor
approx. 26 V or
(PWRC_Mon)
under 21 V.
Generated error
Power supply
when output power
for output
supply voltage
2
voltage
goes over approx.
monitor
26 V or under
(PWRO_Mon)
20 V.
Generates error
Short Circuit
when the short
3
Detection
circuit of the valve
(SC_MonOp)
is detected.
Restore the setting
of short circuit
Restart after
detection error
4
short circuit
after the valve
(SC_RstOp)
short circuit is
cleared.
Generates error
Open Circuit
per channel when
5
Detection
the disconnection
(OC_Mon)
of the valve is
detected.

Output setting

Set output per
during
channel when
6
communication
communication is
∗ 1
fault
abnormal.
(Fault_MD )
Output setting
Output setting per
during
channel at the time
7
communication
of communication
∗ 1
idling
idling 
(Idle_MD )
Definition
Item
Enable
Disable 
Enable
Disable 
Enable
Disable 
Auto
Manual 
Enable
Disable 
Clear
Hold 
ForceON 
Clear
Hold 
ForceON 
Content
Generates an error.
Does not generate an
error. 
Generates an error.
Does not generate an
error. 
Generates an error.
Does not generate an
error. 
Error is automatically
cleared when the short
circuit is fixed.
Even when the short
circuit is fixed, error is not
cleared until the power is
supplied again. 
Generates an error.
Does not generate an
error. 
Turn off the output
Hold the output 
Turn on the output
forcefully 
Turn off the output
Hold the output 
Turn on the output
forcefully 
-41-
Parameter
setting 
Default
By
setting
By
Ether
H.T.
CAT
 
 
 
 
○ 
 
 
 
 
No.EX##-OMO0027