Specification - SMC Networks EX600-SEC Series Operation Manual

Fieldbus system, ethercat compatible si unit
Table of Contents

Advertisement

Specification

■Specifications
Model
Protocol
Communication speed
Occupied area
(Number of inputs/outputs)
Internal current consumption
(The power supply for control and
input)
Polarity of output
Number of Outputs
Connected load
Power supply
Output condition at the time
of communication error
Protective function
Enclosure
Operating temperature range
Storage temperature range
Operating humidity range
Withstand voltage
Insulation resistance
Pollution degree
Standard
Weight
∗1: All unused connectors must have a seal cap fitted.
∗2: The UL compliant temperature is 0 to 50
EX600-SEC1
EtherCAT (Conformance Test Record V.1.2)
(512 inputs/512 outputs) Max.
PNP (-common)
32 outputs (8/16/24/32 outputs selectable)
24 VDC 1.5 W (SMC) solenoid valve with circuit protection of surge voltage
IP67 (With manifold assembled)
35 to 85%R.H. (No condensation)
500 VAC for 1 minute between external terminals and F.E.
500 VDC, 10 MΩ or more between external terminals and F.E.
For use in Pollution Degree 3 Environment (UL508)
o
C.
-23-
100 Mbps
100 mA or less
NPN (+common)
24 VDC 2 A
HOLD/CLEAR/Force ON
Short circuit protection
o
∗ 2
-10 to 50
C
o
-20 to 60
C
CE, UL(CSA), RoHS
300 g
EX600-SEC2
∗ 1
No.EX##-OMO0027

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ex600-ed seriesEx600-sec1Ex600-sec2

Table of Contents