•Digital output unit parameters
Parameter
No.
(H.T. Symbol)
Generates error
Output load
per unit when the
short circuit
1
short circuit of the
detection
output device is
(SC_MonOp)
detected.
Restore the setting
Restart after
of short circuit
output load
detection error per
2
short circuit
unit after the output
(SC_RstOp)
device short circuit
is cleared.
Generates error
Open circuit
per channel when
3
detection
the disconnection
(OC_Mon)
of the output
device is detected.
Output setting
Set output per
during
channel when
4
communication
communication is
∗ 2
fault
abnormal.
(Fault_MD)
Output setting
Set output per
during
channel during
5
communication
communication
∗ 2
idling
idling.
(Idle_MD)
Memorizes the
number of times
Output
the output device is
ON/OFF
ON. Generates
6
counter
error per channel
(Counter)
when the operation
count exceeds the
set value.
∗1: Could be incorrectly recognized as short circuit depending on used load (ex.: lamp load). If detection is incorrect, disable the
parameter setting.
∗2: This master is valid only when "Hold/Clear priority" of the system parameter is set to Handheld.
∗3: The count is memorized every hour. When the power supply is turned on again, counting starts from the last value memorized.
∗4: Times for setting is set value x1000 times.
Definition
Item
Enable
Disable
∗ 1
Auto
Manual
Enable
Disable
Clear
Hold
ForceON
Clear
Hold
ForceON
Enable
Disable
∗ 3
Content
Generates an error.
Does not generate an
error.
Error is automatically
cleared when the short
circuit is fixed.
Even when the short
circuit is fixed, error is not
cleared until the power is
supplied again.
Generates an error.
Does not generate an
error.
Turn off the output
Hold the output
Turn on the output
forcefully
Turn off the output
Hold the output
Turn on the output
forcefully
Generates an error.
∗ 4
Val: 1 to 65000
Does not generate an
error.
-44-
Parameter
setting
Default
By
setting
By
Ether
H.T.
CAT
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
No.EX##-OMO0027