Details Of Diagnostic Data - SMC Networks EX600-SEC Series Operation Manual

Fieldbus system, ethercat compatible si unit
Table of Contents

Advertisement

■Details of diagnostic data

•System diagnosis
•System diagnosis byte0
Bit No.
0
The analogue value has fallen below the user set value.
1
The analogue value has exceeded the user set value.
2
The analogue input value has fallen below the set range.
3
The analogue input value has exceeded the set range.
4
ON/OFF count has exceeded the set value.
5
The open circuit has been detected.
6
The short circuit of the valve output or digital output has been detected.
7
The short circuit of the power supply for the input/output device has been detected.
•System diagnosis byte1
Bit No.
0
The power supply voltage for output device is outside of the specification.
1
The power supply voltage for control and input device is outside of the specification.
2
Reserved
3
There is a connection failure between each unit (During operation).
4
There is a connection failure between each unit (When the power supply is applied).
5
Reserved
6
System error occurred.
7
Hardware error occurred.
•System diagnosis byte2
Bit No.
0
Reserved
:
:
7
Reserved
•System diagnosis byte3
Bit No.
0
There is an error in the Digital input unit.
1
There is an error in the Digital output unit.
2
There is an error in the Analogue input unit.
3
There is an error in the Analogue output unit.
4
There is an error in the SI unit.
5
Reserved
6
Reserved
7
Reserved
∗1: When the error occurs in the Digital I/O unit, both Bit0 and Bit1 are turned on.
∗2: When the error occurs in the Analogue I/O unit, both Bit2 and Bit3 are turned on.
Content of diagnosis
Content of diagnosis
Content of diagnosis
Content of diagnosis
∗ 1
∗ 1
∗2
∗ 2
-66-
No.EX##-OMO0027