Follow these steps to set up a Pump Control Module
(PD) using the keypad and display. For complete
warnings and operation instructions, see the E-Flo
DC Control Module Kit manual 3A2527.
• Press the Enter key to enter each setting.
• Press the Up Arrow or Down Arrow key to select
the settings for the pump.
• Press the Enter key to enter the selection for the
setting.
1. Press the Toggle key to enter the control module
Setup screens.
2. Use the Up Arrow and Down Arrow keys to
navigate to Setup Screen 14.
Figure 47 Setup Screen 14
3. Confirm that Pump 1 is displayed on the Pump
No. menu
and select 1.
Figure 48 Setup Screen 14 Pump Menu
3A4030C
Module for
Module
for Modbus
for
Modbus Communication
Modbus
. If not, highlight the menu
Communication
Communication
4. Select a control location (local or remote) from
the menu.
Figure 49 Setup Screen 14 Local or Remote
Control Location Menu
5. Set the Modbus node ID from 1 to 247.
Figure 50 Setup Screen 14 Modbus Node ID
Field
6. Select the serial port baud rate from the menu.
57600 bps is standard. 38400 is also available.
Do not select 115200 because it is not compatible
with the Supervisor Module.
Figure 51 Setup Screen 14 Baud Rate Menu
7. When all control module settings are correct,
press the Exit Screen key to exit setup mode.
Software Setup
47