Intelligent Paint Kitchen Overview
Pump
Pump Control
Pump
Control
Control Module
Module (PD)
Module
24P822,
24P822, 17V232
24P822,
17V232
17V232
The Pump Control Module (PD) is a Modbus RTU
node in the station. Each Pump Control Module is
wired using a pair of fiber optic cables to a fiber optic
converter installed inside a Supervisor Box (A).
All communications between components on the
non-hazardous location and the hazardous location
sides pass to or from the Pump Control Module along
the fiber optic connection.
The Pump Control Module serves as the connection
point and power source for other paint kitchen
components, including the Radar Level Sensor
(M, T), Fill Pump Transfer Solenoid (P), and Back
Pressure Regulator Controller (F).
Power to the Pump Control Module is supplied by
the E-Flo DC pump (C). Each Pump Control Module
has its own software installed to send instructions
from the Intelligent Paint Kitchen software to the
connected components, and to send signals from
those components back to the Intelligent Paint
Kitchen software.
Figure 4 Pump Control Module
For information on connecting cables to the correct
ports for pump control, see the cable connection
section of the DC Control Module Kit manual 3A2527
and
Set Up Pump Control Module Configurable
I/O, page 49
in this manual. See the DC Control
Module Kit manual 3A2527 for complete warnings
and operation instructions.
12
(PD)
(PD)
Pressure Transducer
Pressure
Pressure
Transducer (K)
Transducer
24R050,
24R050, 24X089
24R050,
24X089
24X089
Install the Pressure Transducer (K) using one of the
following kits:
• 24R050: Pressure Transducer, NPT
• 24X089: Pressure Transducer, Inline Tri-Clamp
1. To measure fluid pressure, install the Pressure
Transducer in the fluid line with a tee fitting.
• If closed loop control is enabled on Setup
Screen 8 (transducer 1) or Setup Screen 9
(transducer 2), install the transducer near the
pump outlet, not near the end of the circulation
line.
• If closed loop control is not enabled on Setup
Screen 8 (transducer 1) or Setup Screen 9
(transducer 2), install the transducer where
needed.
2. Connect the transducer cable to Port 7
(transducer 1) or Port 10 (transducer 2) on the
Pump Control Module (PD) or Tank Control
Module (TD).
(K)
(K)
3A4030C