SENSOR SETTING

1)
When sensors are reselected, the sensor curves will be transferred into the standard value. For
example, if temperature sensor is SGD (120°C resistor type), its sensor curve is SGD (120°C resistor
type); if select the SGH (120°C resistor type), the temperature sensor curve is SGH curve.
2)
When there is difference between standard sensor curves and used sensor curves, users can
adjust it in the "sensor curve type".
3)
When the sensor curve is inputted, x value (resistor) must be inputted from small to large,
otherwise, mistake occurs.
4)
If sensor type is selected as "none", sensor curve is not working.
5)
If the corresponding sensor has alarm switch only, users must set this sensor as "none", otherwise,
shutdown or warning may occur.
6)
The headmost or backmost values in the vertical coordinates can be set as the same as below.
1Pa
1kgf/cm
2
1bar
1psi
HGM9520N Genset Paralleled Controller User Manual
Fig. 4 Sensor Curve Diagram
Table 21 Normal Pressure Unit Conversion Form
pa
kgf/cm
1
1.02x10
9.8x10
4
1x10
5
6.89x10
3
7.03x10
2
bar
5
1x10
1
0.98
1.02
2
6.89x10
psi
5
1.45x10
14.2
1
14.5
2
1