Liquid Level Sensor
4
Power Transmitter
5
Irradiance sensor
NOTE: pressure sensor and flexible sensor 1 connected input signals are resistor, current and voltage signals.
When configuring "custom current/voltage curve" via controller penal, X coordinate data need to be expanded tenfold,
for example, for 4mA, input data is "40". When setting the "custom 0-5V curve" through the controller panel, the
x-coordinate data should be enlarged by 100 times, such as 4V input data "400".
SENSOR SETTING
6.6
—
When sensors are reselected, the sensor curve will be transferred into the standard value. For
example, if temperature sensor is SGH (120° C resistor type) at default factory, its sensor curve is
SGH (120° C resistor type); if SGD (120° C resistor type) is selected, the temperature sensor
curve is SGD curve.
—
If there is difference between standard sensor curves and the used sensor, users can select
"defined sensor", and then input defined sensor curve.
—
When the sensor curve is inputted, X value (resistor) must be inputted from small to large,
otherwise, mistake occurs.
—
If sensor is selected as "Not Used", sensor curve will not work.
—
The corresponding sensor must be configured as "Not Used" if sensor only has alarm switch,
otherwise, alarm shutdown or warning may occur.
—
The headmost or backmost values in the vertical coordinates can be set as same as below.
HES7120-PV Hybrid Engergy Controller
HES7120-PV HYBRID ENERGY CONTROLLER USER MANUAL
Description
0 Not used
1 Custom resistor type curve
2 Custom curve 20mA-4 curve
3 Custom curve 0-5V curve
4:SGD
5:SGH
6:SUZUKI
7-15 Reserved
0 Not used
1 Custom resistor type curve
2 Custom curve 20mA-4 curve
3 Custom curve 0-5V curve
4-15 Reserved
0 Not used
1 Custom resistor type curve
2 Custom curve 20mA-4 curve
3 Custom curve 0-5V curve
4-15 Reserved
2020-05-20
Remark
Defined
resistance's
range is 0~6KΩ, default
is not used.
Defined
resistance's
range is 0~6KΩ, default
is not used.
Defined
resistance's
range is 0~6KΩ, default
is not used.