9 SENSOR SETTING

1) When sensors are reselected, the sensor curve will be transferred into the standard value. For
example, if temperature sensor is SGH (120° C resistor type), its sensor curve is SGH (120° C
resistor type); if select the SGD (120° C resistor type), the temperature sensor curve is SGD curve.
2) When there is difference between standard sensor curves and used sensor, users can select
"custom sensors" and then input custom sensor curve.
3) When users input the sensor curve, X value (resistor) must be inputted from small to large,
otherwise, mistake occurs.
4) When sensor is selected as "Not Used", LCD displays temperature, pressure and fuel level as "- -
-".
5) If there is not oil pressure sensor, but there is low oil pressure alarm switch, users must set the oil
pressure sensor as "None", otherwise, maybe low oil pressure shutdown occurs.
6) The headmost or backmost values in the vertical coordinates can be set as same as below.
1Pa
2
1kgf/cm
1bar
1psi
HGM8140 Military Genset Controller
HGM8140 MILITARY GENSET CONTROLLER USER MANUAL
Fig. 6 Pressure Sensor Curve
Table 15 Common Unit Conversion Table
2
N/m
Pa
1
4
9.8x10
5
1x10
3
6.89x10
2
kgf/cm
5
1.02x10
1
2
1.0
2
7.03x10
Version 1.2
2019-09-12
bar
5
1x10
1.45x10
0.98
1
2
6.89x10
Page 40 of 56
psi
4
14.2
14.5
1