SENSOR SETTING
— When choosing sensor, standard value of sensor curve will be needed. If temperature sensor is set
as SGH (120ºC resistor type), sensor curve should be SGH (120ºC resistor type); If it is set as SGD
(120ºC resistor type), sensor curve should be SGD curve.
— If there is difference between standard sensor curve and chosen sensor curve, select "defined
sensor", and then input defined sensor curve.
— When sensor curve is inputted, X value (resistance) must be in accordance with the order of higher
to lower, otherwise errors will occur.
— When sensor is selected as "Not used", temperature, pressure and fuel level will be display as "- -
-" in LCD.
— If there is no pressure sensor, but only has low pressure alarm switch, then you must set pressure
sensor as "Not used", otherwise oil pressure low alarm shutdown may appear.
— Can set several points of forehand or backmost as the same ordinate, as the following picture:
1N/m
1Pa
1kgf/cm
2
9.8x10
1bar
1psi
6.89x10
HGM6100N Series Genset Controller User Manual
Fig.4 – Sensor Curve Diagram
Table 12 – Conventional Pressure Unit Conversion Table
2
(pa)
1kgf/cm
1
1.02x10
4
1x10
5
3
7.03x10
2
-
5
1x10
1
1.02
-
2
6.89x10
1bar
(1b/in
-
5
1.45x10
0.98
1
-
2
Page 32 of 47
2
) psi
-
4
14.2
14.5
1